2.4.2

BATTERY CONNECTION

-
Take care not to cause electric shock or chemical hazards
-
Plug in the DC circuit breaker (≥ 40A) between the battery and the inverter.
Make sure your batteries are switched off before connecting and the ET series is disconnected from
the FV and AC sides[4].
Follow strictly the instructions below.
Using the wrong conductor can result in poor contact and high impedance, which is dangerous for the
system.
-
Use the correct BAT connector from the accessories.
-
Use tinned cables with a 4 to 6 mm2 (AWG 10) cross-section, as the maximum battery current is 25A.
Adjust the cable to connect the battery according to the picture below
Connect the battery according to the following steps:
Step 1
Using a screwdriver, open the clip
Step 3
Insert the insert into the connector (C).
Tighten the cap with 2 Nm (D).
Use a suitable and calibrated size 15 torque wrench
and hold the connector open with a size 16 wrench
while tightening.
* To install compatible lithium batteries (Pylon/BYD), read the ET QUICK INSTALLATION MANUAL.
Marking
Description
A
Outer diameter
B
Conductor cross-section
C
Stripped wire length
Step 2
Carefully insert the stripped and twisted wire into the
connector (A). The end of the wire must be visible
under the clip. Snap the clip. Make sure the clip holds
the cable (B).
Step 4
A click should be heard when the connector is inserted.
After clicking, check that the connectors really hold.
Value
5.5-8.0 mm
4-6 mm2
15 mm