2.4 WIRING
2.4.1
PV CONNECTION
Before connecting the PV panels/strings to the changer, check the following points:
The total shortcircuit current of the panels is no higher than the max input DC of the
inverter. (for GW8KL-ET and GW10KL-ET, the PV2 has two pairs of connectors, allowing
two strings to be connected with a total short circuit current not exceeding 22A).
The insulation resistance of the PV panels against the ground must be more than 33.33k,
otherwise, there is a risk of electric shock.
The PV string should not be attached to the ground.
Use the attached connectors to connect the PV strings. (THE BAT connector is similar to
the PV connector, check the connectors thoroughly before connecting)
NOTE: Accessories include either MC4 or QC4.10 connectors or Amphenol, the detailed connection is shown
below.
Step 1
Note:
-
Use the PV connectors included in the package
-
Use a PV cable with a cross-section of 2.5-4 mm2
Step 2
Connect the PV cable with the PV connector
Note:
-
The PV cable must be tightly pressed with the connector
-
For the Amphenol connector, use a limiting clip, it must not be pressed. There must be a click when
the connector is assembled
Step 3
Pull the cap onto the connector
Note:
-
You should hear a click when the connector is inserted
The polarity of the PV input must not be reversed, otherwise, there is a risk of destroying the inverter [3]
For GW8KL-ET and GW10KL-ET, if the PV array you connect to the PV2 input has a short-circuit current
higher than 15A, divide the PV array into two strings and connect two pairs of connectors to the PV2
input.