Output Mode

(Available on MCA/MCP Only)
Options: Auto, Manual
/<Maintenance>/Output
SET
• The Manual Output Mode provides a way to bypass the control logic to adjust the
modulating output manually.
• The Output mode is primarily used for equipment testing and troubleshooting.
• When set to Manual, the Output Amount menu can be adjust the amount of manual
modulation as a percent of the total range.
• When in Manual, the output will modulate to the set percent regardless of the Enable/
Disable, the outdoor Cutoff, or sensor fault status.
• To revert to control PID operation, the Output Mode must be set to Auto.

valve Mode

(Available on MCF Only)
Options: Auto, Close, Open
SET
/<Maintenance>/Valve
• The Valve Mode provides a way to manually bypass the control PID logic and open or
close the valve.
• The Valve mode is primarily used for equipment testing and troubleshooting.
• To revert to control PID operation, the Output Mode must be set to Auto.
18
Default: Auto
Default: Auto
MC-Elite Installation and Operation Manual
Output Mode:
Auto
Manual
Output Amount:
50%
Valve Mode:
Auto
Close
Open