MC ELItE Output MODEs WIrIng

MCA Modulating a Voltage Actuator
®
o
SYSTEM =
147
F
o
TARGET =
150
F
Decrease
DECREASE
INCREASE
System
SYSTEM
Not Used (White)
MCA Modulating a Voltage Boiler
®
o
SYSTEM =
147
F
o
TARGET =
150
F
DECREASE
INCREASE
SYSTEM
Decrease
System
Not Used (White)
MCF Modulating a Floating Actuator
®
o
SYSTEM =
147
F
o
TARGET =
150
F
DECREASE
INCREASE
SYSTEM
Decrease
System
Transformer
• The MC Elite does not source any power to any of its output relays. When connecting the output to a pump, an external
power source must supply the pump or its starter with power. Wire the system output (Yellow wires) so that it make or
break the hot leg.
• Heat-Timer DOES NOT recommend sharing the power source to the control with any pumps or heavy electric equipment.
• Heat-Timer Corp. is aware that each installation is unique. Thus, Heat-Timer Corp. is not responsible for any installation
related to any electrical or plumbing diagram generated by Heat-Timer Corp. The provided illustrations are to demonstrate
Heat-Timer Corp.'s control operating concept only.
MC-Elite Installation and Operation Manual
System Pump
120 VAC
(Yellow)
120 VAC
Power (Black)
Common (Red)
Voltage
Voltage (Blue)
Signal
Voltage
Modulating
Motorized Valve
System Pump
120 VAC
(Yellow)
120 VAC
Power (Black)
Common (Red)
Voltage
Voltage (Blue)
Signal
Voltage
Modulating
Boiler
System Pump
120 VAC
(Yellow)
120 VAC
Power (Black)
Close (Blue)
Close
Open (White)
Open
Common (Red)
Comm
Floating
120VAC
Motorized Valve
MCA Modulating a 4-20mA Actuator
®
o
SYSTEM =
147
o
TARGET =
150
F
Decrease
DECREASE
INCREASE
System
SYSTEM
MCA Modulating a 4-20mA Boiler
®
o
SYSTEM =
147
o
TARGET =
150
F
DECREASE
INCREASE
SYSTEM
Decrease
System
MCP Modulating a 135Ω Boiler
®
o
SYSTEM =
147
o
TARGET =
150
F
DECREASE
INCREASE
SYSTEM
Decrease
System
ALErt
System Pump
(Yellow)
F
Power (Black)
Common (Red)
4-20mA (White)
+ -
30-36VDC
Excitation
Not Used (Blue)
Voltage
Motorized Valve
System Pump
(Yellow)
F
Power (Black)
Common (Red)
4-20mA (White)
+ -
30-36VDC
Excitation
Not Used (Blue)
Voltage
Power (Black)
Boiler Activation
F
(Yellow)
Red
White
Blue
135Ω
Signal
135Ω
Modulating
Boiler
120 VAC
120 VAC
Current
Signal
4-20mA
Modulating
120 VAC
120 VAC
Current
Signal
4-20mA
Modulating
Boiler
120 VAC
21