Run-On; Maintenance Settings; Maintenance Menus; System And Outdoor Trim - heat-timer DIGI-SPAN Elite MC Series Installation And Operation Manual

Table of Contents

Advertisement

run-On

Options: From 0 min to 60 min
/<Settings>/Run-On
SET
• If the Relay Output was set to Pump, the System relay will energize whenever the outdoor
temperature is below the outdoor Cutoff in heating or above it in cooling. See "Relay
Output" on page 12. When the outdoor temperature increases 2°F above the outdoor Cutoff
or when the EXT+ and EXT- terminal inputs are opened, the output relay will stay on for
the Run-On period. This allows the system to dissipate the residual energy within its units
back into the system.
• The Run-On time should be set based on the size and type of the equipment controlled.

MAIntEnAnCE sEttIngs

Default screen
SYSTEM=
TARGET=
SET
------MAIN------
Set Point
70 F
<Out. Reset>
<Settings>
SET
<Maintenance>
<Sys. Startup>
<Info>
<Back>
SET

system and Outdoor trim

Options: varies based on sensor type . see "sensor trim table" on page 17 .
/<Maintenance>/Sys. Trm or Out. Trim
SET
• The Heat-Timer system sensors are very accurate, and normally require no calibration.
SET
However, sometimes it may be desirable to make small adjustments to the displayed value.
• Do not use the Trim setting to make the Outdoor sensor match the one reported on the
radio or TV. The outdoor temperature can vary widely over a broadcast range.

sensor trim table

TRIM (Default=0)
EngLIsh sEnsOr
typE
Temp. 230˚F (SYS)
-20˚F to +20˚F
Temp. 230˚F (OD)
-20˚F to +20˚F
Pressure 30 PSI
-3.0 to +3.0 PSI
Pressure 100 PSI
Pressure 200 PSI
-20 to +20 PSI
Pressure 300 PSI
-30 to +30 PSI
Vacuum 30 Hg
-3.0 to +3.0 Hg
Humidity
+10 to -10%RH
MC-Elite Installation and Operation Manual

Maintenance Menus

--MAINTENANCE--
68 F
150 F
Sys. Trim
Out. Trim
Output
Valve
<Back>
Valve Mode:
Auto
Close
Open
MEtrIC sEnsOr
typE
range
Temp. 120˚C (SYS)
Temp. 120˚C (OD)
Pressure 0.250 MPa
-10 to 10 PSI
Pressure 0.600 MPa
Pressure 1.000 MPa
Pressure 1.600 MPa
Vacuum 760 mm
Default: 2 min
+0 F
+0 F
Auto
Auto
sEnsOr
TRIM (Default=0)
tErMInALs
range
-11˚C to +11˚C
T1, COM
-11˚C to +11˚C
T2, COM
-0.025 to +0.025 MPa
P+, P-
-0.06 to +0.06 MPa
P+, P-
-0.1 to +0.1 MPa
P+, P-
-0.16 to +0.16 MPa
P+, P-
-80 to +80 mm
P+, P-
P+, P-
Relay Run-On:
2.0m
System Trim:
+0 F
Outdoor Trim:
+0 F
Output Mode:
Auto
Manual
Output Amount:
50%
System Trim:
+0 F
Outdoor Trim:
+0 F