Steam Heating Features; Steam Outdoor Reset; Night (Sleep) Setback; Day And Night Schedules - heat-timer Genesis Installation And Operation Manual

Light commercial internet base control
Table of Contents

Advertisement

STEAM HEATING FEATURES

STEAM OUTDOOR RESET

The Genesis Heat-Timer
®
concept based on the Day and Night Heat Adjustment and Outdoor start to regulate the heat. The colder it gets, the longer the
Cycle-On runs.

NIGHT (SLEEP) SETBACK

Whenever the outdoor temperature falls below the Outdoor start, the Genesis Heat-Timer
Cycle-OFF ratio to hold a constant Day or Night heat level. The Night heat level is for when the building is unoccupied or
tenants are sleeping.

DAY AND NIGHT SCHEDULES

®
The Genesis Heat-Timer
day of the week. By setting a Schedule, Day and Night Heat Adjustments, and Outdoor start, you can save energy while providing
comfortable heat to the building. The Night (AWAY/SLEEP) settings allow the Genesis Heat-Timer
steam Cycle-ON portion during the night or when building is unoccupied. Each schedule period can have an individual desired
building temperature setting.

SYSTEM OUTPUT

The system output relay connects to and operates a combustion air-damper or other boiler room equipment and it will energize
whenever there is a call for the boiler.

BOOST AND EARLY SHUTDOWN

The Boost is designed to return the building to its Day (WAKE) heat level after Night (SLEEP) heat level. It does it by running the
burner or valve output for a period of time that depends on the outside temperature.
The Early Shutdown is a feature that shifts the Day schedule to Night Setback before the last Night (SLEEP) setting for that day.
The Early Shutdown varies based on Outdoor temperature (OD). The warmer the Outdoor temperature the earlier the
Genesis Heat-Timer
®
Heat-Timer
NOTE
The BOOST and EARLY SHUTDOWN features are only accessible online through ICMS (Internet Control
Management System).
|
14
HEAT-TIMER CORP.
regulates the amount of steam sent to the building based on the outdoor temperature. It uses the Cycle
has 2 Day (WAKE AND RETURN) and 2 Night (AWAY AND SLEEP) Schedule Period settings for each
®
shifts to Night Setback.
03
STEAM HEATING
®
adjusts the Cycle-ON and
®
to reduce the length of the
059705–00 REV. B