4.2 Protective bonding

It is necessary to interconnect cabinet chassis with main earthing point, to ensure equal potential
throughout the installation thus preventing a hazardous potential difference occurring between such
parts in the event of a fault.
Connect bonding cable from main earthing point to the bonding point on the bottom of the cabinet with
M6 lug.
Main earthing point
NOTE:
Do NOT interconnect bonding busbars in multiple cabinets in multicabinet installation. Connect
separate bonding cable to each cabinet in multicabinet installation.
Installation Guide ● PowerShaper 2.0
Figure 4.2 Protective bonding