1.2.2 Air Conditioner with Heat Exchanger

The HC series Air Conditioner with Heat Exchanger is a cooling product developed for cabinets. It is
applicable for the scenarios where internal equipment of the cabinet emits a large quantity of heat
and needs to be isolated from the outdoor environment completely. The unit integrates the heat pipe
exchanger with air conditioner. When the external ambient temperature is lower than the cabinet inner
temperature, the heat pipe exchanger takes precedence to work, and realize reduce heat-dissipating
consumption.
The operating principle of Air Conditioner with Heat Exchanger is shown in
system and air conditioner share the same indoor/outdoor fans.
The heat exchanger and the compressor of the Air Conditioner with Heat Exchanger adopt grading
interlocking control. The heat exchanger is defined as the first level heat dissipation and the compressor
is defined as the second level cooling. According to the cabinet internal/external temperatures, dividing
into four working modes: internal fan running, heat exchanger running, air conditioner running and both
running.
NOTE:
The air conditioner shall be kept vertically strictly in accordance with the instructions on the package
during transportation, storage and use.
Default settings
Aircon is pre-set from factory to the temperature 23°C +/-5°C. If this setting is not acceptable for
conditions on site, set appropriate temperatures following instructions in the
Conditioner with Heat Exchanger.
Installation Guide ● PowerShaper 2.0
10
Side View
Figure 1.2 Air condition air flow diagram (side view)
Figure 1.2.
The heat exchange