Fuse List; Anti-Islanding - Pixii PowerShaper 2.0 Installation Manual

Grid tied energy storage system
Table of Contents

Advertisement

1.4.4 Fuse list

-FC1
-FC2
-FC13 10A 6.4x32mm fast 10kA
-FC14 10A 6.4x32mm fast 10kA
-FC20 10A 6,4x32mm fast 10kA
-FC21 10A 6,4x32mm fast 10kA
F201
F202
F203
NOTE:
Please consult replacement of any fuse or circuit breaker with Pixii first.

1.5 Anti-islanding

The PowerShaper incorporates both passive and active anti-islanding functionality. The passive methods
included are under/over voltage, under/over frequency and rate of change of frequency detection. The
active anti-islanding functionality uses the frequency shift method based on feedback from frequency
variation in combination with a small reactive power perturbation. The active anti-islanding function may
be disabled for grid codes not accepting such means of islanding detection.
Installation Guide ● PowerShaper 2.0
16
Type
100A 4-pole C-curve
10A 2-pole B-curve
0,5A 5x20mm slow
3,15A 5x20mm slow
3,15A 5x20mm slow
Manufacturer
Manufacturer part number
Schneider
A9N18374 (AS/NZS 60898.1:2004)
Schneider
A9F53210 (AS/NZS 60898.1:2004)
Littelfuse
Littelfuse
Bussmann
Bussmann
Littelfuse
Littelfuse
Littelfuse
A9N18480
A9F03210
AHC-10-R
AHC-10-R
ABC-10-R
ABC-10-R
0477.500MXP
04773.15MXP
04773.15MXP
Introduction