2.4 Demand response modes (DRM)

The PowerShaper supports all Demand Response Modes specified in AS/NZS 4777.2 with the responses
shown in the table below.
Mode
DRM 0
DRM 1
DRM 2
DRM 3
DRM 4
DRM 5
DRM 6
DRM 7
DRM 8
In order to activate the different Demand Response Modes, a Demand Response Enabling Device
(DRED) as described in AS/NZS 4777.2 must be connected to the DRM-port of the PowerShaper. The
DRM-port (-TF2) of the PowerShaper is utilized as an RJ45-connector -X22 located in the bottom of the
cabinet as indicated by the picture below.
Installation Guide ● PowerShaper 2.0
20
Response
Disconnect the system from the grid
Active Power consumption limited to 0%
Active Power consumption limited to 50%
Active Power consumption limited to 75%
Reactive Power set to max sourcing (capacitively)
Increase power consumption
Active Power generation limited to 0%
Active Power generation limited to 50%
Active Power generation limited to 75%
Reactive Power set to max sinking (inductively)
Increase power generation
Figure 2.2 DRM interface
Enabled by shorting pins
5
6
1
6
2
6
3
6
4
6
5
1
5
2
5
3
5
4
Preparing installation site