Pulse input totalizer / batch / immediate value for flowmeter or lengh/rpm controller

Advertisement

RELAY GRUOP
ENT
F N
Next P.
DESCRIPTION
RELAY GROUP INDEX
rY.Sb: Start band of Relay Output
Start Delay
Energized / De-energized
Delay & Hysteresis
Inhibit
Hi Setting
Inhibit
Hi Setting
Start Band
Relay
Relay
ON
Start Delay Time
Energized
Energized
rY.Sd: Relay Output start delay time
rY1.Md: Relay 1 energized mode
Relative Immediate Value(PV): Hi / Lo / Go
Hi / Lo / Go Relay
Hi(Lo) Energized Hold &
Energized
Reset
Hi Setting
Lo Setting
Hi.HLd(High Hold)
Hi RL Energized
ON
Relay Energized
ON
Lo RL Energized
Reset the relay Hold
by ECI or Front Key
Go RL Energized
ON
ON
Relative Totalizer / Batch / Batch Counter:
N / R / C Mode
N MODE:
Manual
Totalizer
Set
Reset
When the condition of Set Point is met:
Point
1. the relay will be energized;
2. The totalizer will run as same as
usual; until manual reset by front key
or by rear terminal, the totalizer will
be reseted to "0" and the relay will be
Relay
de-energized.
Output
ON
R MODE:
When the condition of Set Point is met:
Auto
Set
Reset
1. The relay will be energized; until the
Point
time is over Relay output time
rY.1(2).ot(Relay1(2) output time).
Totalizer
2. The totalizer will run as same as
usual; until the time is over Relay output
Relay output Time
time rY.1(2).ot(Relay1(2) output
Relay
time),The totalizer will be reset to "0".
Output
ON
Auto
C MODE:
Set
Totalizer
Reset
When the condition of Set Point is met:
Point
1. The relay will be energized; until the
time is over Relay output time rY.1.ot
or rY.2.ot .
Relay output Time
2. The totalizer will be reset to "0", then
counts-up from "0".
Relay
Output
ON
The page will show out, when rY1.Md set
to be N/R/C mode.
rY1.ot: Relay 1 energized time
The page will show out, when rY1.Md set
to be Hi/Lo mode.
rY1.HY: Relay 1 Hysteresis
The page will show out, when rY1.Md set
to be Hi/Lo mode.
rY1.rd: Relay 1 energized delay time
The page will show out, when rY1.Md set
to be Hi/Lo mode.
rY1.Fd: Relay 1 de-energized delay
time
In following page, press
RELAY GROUP INDEX.
Setting Range: 0~9999 counts
Shift
Hysteresis
ON
Setting Range:
0:00.0~9(M):59.9(S)
Shift
Selectable:
oFF:Turn off the Relay and
relative LED.
Lo:Low Level Energized; Relay
will energize when PV <
Hi Setting
Set-Point.
Hi:High Level Energized; Relay
ON
will energize when PV >
ON
Level T rigger
Set-Point.
Hi.HLd / Lo.HLd:High / Low
Level energized latch; When
the PV Higher (or lower) than
set-point, the relay will be
energized and hold until
manual reset by from key in
【User Level】or【E.C.I.】.
do:Digital Output; Relay is
energized by RS485 command
directly, and no longer to
compare with set-point of
relay.
btcH.n: Batch control with N
mode energized.
btCH.r: Batch control with R
mode energized
btCH.C: Batch control with C
mode energized.
totL.n: Totalizer control with N
mode energized.
totL.r: Totalizer control with R
mode energized.
totL.C: Totalizer control with C
mode energized.
Up
Setting Range:
0:00.0~9(M):59.9(S)
Shift
Setting Range: 0~5000 counts
Shift
Setting Range:
0:00.0~9(M):59.9(S)
Shift
Setting Range:
0:00.0~9(M):59.9(S)
Shift
17 / 27
PARAMETERS
for 1 second to back
Up
Down
Enter
Up
Down
Enter
Down
Enter
Up
Down
Enter
Up
Down
Enter
Up
Down
Enter
Up
Down
Enter
CS2-TM(Pulse)-Operating Manual 2012-05-10