Psychrometric Chart Showing Recommended And Allowable Operating Environments For The Tape Library; Equipment Environment Specifications For The Ts1170 Drive Model - IBM TS4300 User Manual
• The chart is shown in SI (metric) units and a barometric pressure of 101.325 kPa (sea level).
• The recommended operating environment specifies a long-term operating environment that can result
in the greatest reliability and energy efficiency.
• The allowable operating environment represents where the equipment has been tested to verify
functionality.
Figure 20. Psychrometric chart showing recommended and allowable operating environments for the tape
library
Table 19. Equipment environment specifications for the TS1170 drive model
Dry-bulb temperature
Allowable/
Maximum rate of
Recommended 3
change
15 to 25°C
5°C/hour
(60 to 77°F)
(9°F/hour)
Notes:
1. Product equipment is removed from the original shipping container and installed but not in use - for example, during repair, maintenance, or upgrade.
2. Derate maximum dry-bulb temperature 1°C/300 m above 900 m (1.8°F/1,000 feet above 3,000 feet).
3. Derate maximum recommended dry-bulb temperature 1°C/300 m above 1,800 m (1.8°F/1,000 feet above 6,000 feet).
4. Changes of up to 30% RH in 5 minutes are allowed as long as the 20% to 50% absolute limits are not exceeded.
30 IBM TS4300 Tape Library Machine Type 3555: User's Guide