SYSTEM OPTIONS

SYSTEM OPTIONS
CRS ZONE TM:
4
RETARD DLY:
10
PWR FAIL HRS:
1
SWGRBYPS TRIPS:
2
YES
TIME CHG
NO
HRS FROM GMT:
6
GMT
*Arizona, Hawaii, American Samoa, Guam, Puerto Rico, and the Virgin Islands do not observe daylight savings time.
Digital Monitoring Products
28
System Options
This section allows you to select system-wide parameters.

Cross Zone Time

Enter the time allowed between zone faults. When zones are cross zoned, the same zone
or a second cross zoned zone must fault within this time in order for an alarm report for
both zones to be sent to the receiver. If the cross zone time expires without the second
zone faulting, only a zone fault from the first zone is reported. Cross-zone time can be from
4 to 250 seconds. Entering 0 (zero) disables this function. Default is 4.

Zone Retard Delay

Enter the retard time assigned to Fire and Supervisory zones. The retard delay only
functions when the zone is shorted. The zone must remain shorted for the entire length
of the Retard Delay before being recognized by the panel. The Zone Retard Delay can be
from 0 to 250 seconds. Entering a 0 (zero) disables this function. Default is 10.

Power Fail Delay

This option tracks the duration of an AC power failure. When the AC power is off for the
length of the programmed delay time, an AC power failure report is sent to the receiver.
The delay time can be from 1 to 15 hours. Entering a 0 (zero) sends the power failure report
after a 15-second delay. The default setting is 1.

Swinger bypass Trips

Enter the number of times (0-6) a zone can go into an alarm or trouble condition within
one hour be fore being auto matically bypassed. Bypassed zones are reset during a sensor
reset. Entering 0 (zero) disables this function. Default is 2. A Bypass Re port is sent to the
receiver if Bypass Re ports is YES.

Time Changes

This function allows the panel to request automatic time changes from the DMP SCS-1R
Receiver on Path 1. For the receiver to send time changes, it must be programmed to send
time changes and must be receiving time change updates from the network automation
computer at least every 24 hours. Default is YES.
Hours From GMT
When time zone is programmed YES, enter the number (0-23) that indicates the difference
between the Greenwich Mean Time (GMT) and where the panel is located. The default is 6.
City/Time Zone
London, Monrovia, Lisbon, Dublin, Casablanca, Edinburgh
0
Cape Verde Island, Azores
1
Mid-Atlantic, Fernando de Noronha
2
Buenos Aires, Georgetown, Brasilia, Rio de Janeiro
3
Atlantic Time (Canada), Caracas, La Paz, Santiago
4
Eastern Time (US, Canada) Bogota, Lima, Arequipa
5
Central Time (US, Canada), Mexico City, Saskatchewan
6
Mountain Time (US, Canada), Edmonton
7
Pacific Time (US, Canada), Tijuana
8
Alaska
9
Hawaii*
10
Midway Island, Samoa
11
Fiji, Marshall Island, Wellington, Auckland, Kwajalein,
12
Kamchatka
GMT
City/Time Zone
13
New Cadelonia
14
Guam, Sydney
15
Tokyo, Seoul
16
Hong Kong, Singapore
17
Bangkok, Hanoi
18
Dhaka, Almaty
19
Islamabad, Karachi
20
Abu Dhabi, Kazan
21
Moscow, Bagdad
22
Eastern Europe
23
Rome, Paris, Berlin
XF6 Series Installation and Programming Guide