DEVICE SETUP

DEVICE SETUP
DEVICE NO: -
* UNUSED *
TYPE: FIRE
FI EXP
Digital Monitoring Products
24
Device Setup
This section allows you to define the panels physical configuration. You can install and
address up to fifteen supervised devices on the keypad bus.

Device Number

Enter the address of the device you are programming. After you program each option for
the first device, repeat these programming steps for each additional device. Programmable
devices are FIRE and EXPANDER. The available addresses are 1 - 16 on the panel keypad
bus.

Device Name

A device name must be given to each device in the system. To add a device name, press
any select key or area. The default device name (DEVICE XX) displays. Select CMD to
accept the default name or press any select key or area to enter a new name up to 32
alphanumeric characters. Press CMD.
To remove a device from the system, delete the device name by pressing any select key or
area, then press CMD. The panel automatically programs the name as * UNUSED *.

Device Type

This section allows you to select a device type for the selected device number.
FIRE ‑ A 7830F Fire Command Keypad or 630F Remote Annunciator. See Fire Device
Remote Programming in the XF6 Series Compliance Guide (LT-2779) for instructions on
how to allow remote panel programming.
EXPANDER ‑ A Zone Expansion Module.