System Options; System; Closing Code; Closing Check - Digital Monitoring Products XTLplus Series Installation And Programming Manual

Table of Contents

Advertisement

SYSTEM OPTIONS

SYSTEM OPTIONS
HOME/AWAY

SYSTEM:

AREA
A/P
H/A
NO YES
CLS CODE
CLS CHK
NO YES
ENTRY DLY 1:
30
60
ENTRY DLY 2:
60
EXIT DLY 2:
XTLplus Series Installation and Programming Guide | Digital Monitoring Products
System Options
This section allows you to select system wide parameters used in the operation of the
XTLplus Series panel.
System
This configures the panel as either a Home/Away system (Perimeter, Interior, and
Bedrooms), an All/Perimeter system (Perimeter/Interior), or a six Area system.
Zones must be assigned to Bedrooms for Sleep to appear on the keypad.

Closing Code

When YES is selected, a user code is required for system arming. If NO is selected, a
user code is not required for system arming. Default is NO.

Closing Check

Select YES to enable the panel to verify that all areas have been armed after a
schedule ends. If the Closing Check finds any areas disarmed past the scheduled time,
all keypads emit a steady beep and display CLOSING TIME. The user must extend the
schedule or arm the system within 10 minutes or a Late to Close message is sent to
the central station. Default is NO.

Entry Delay

Enter the entry delay time for all exit type zones programmed to use Entry Delay 1.
When an armed Exit type zone is faulted, the keypad prewarn tone begins sounding.
ENTER CODE and the name of the zone causing the Entry Delay displays on all
keypads. All Burglary type zones in all areas are delayed along with the Exit zone.
When the first digit of a code is entered, the prewarn tone stops at the keypad. If,
within five seconds, a valid user code is not entered or an invalid user code is entered,
the prewarn tone begins sounding again. Fifteen seconds must elapse before entering
a digit silences the prewarn tone again.
The area must be disarmed before the entry delay expires or an alarm is tripped.
Entry delay times can be from 30 to 250 seconds. Repeat the above for Entry Delay 2
if it is being used. Default is 30 seconds for Entry Delay 1.

Exit Delay

Enter the Exit Delay time for all Exit type zones. When the exit delay time starts, all
activity on exit and burglary zones is ignored until the exit delay expires. The keypad
displays the Exit Delay time countdown and annunciates the Exit Delay tone at 8
second intervals until the last 10 seconds when annunciation is at 3 second intervals.
The exit delay can be from 45 to 250 seconds. Default is 60 seconds.
During Exit Delay, if an exit zone trips, then restores, and trips again, the Exit Delay
timer restarts. This restart can occur only once.
Exit Error Operation
At arming, when an entry/exit zone (EX) is faulted at the end of the exit delay then
one of two sequences occur:
For Entry Delay 1 EX Type Zones
The bell sounds for the length of time set in Bell Cutoff programming
The Entry Delay operation starts, requiring code entry to disarm
If not disarmed, a zone alarm and an Exit Error are sent to the receiver
For Entry Delay 2 EX Type Zones
The zone is force armed and a zone force arm message is sent to the receiver
An Exit Error is sent to the receiver
The bell sounds for the length of time set in Bell Cutoff programming
24