ZONES

Terminals 17-28
Zones 1 to 6 (Terminals 17 to 28) on the panel are 24 VDC powered zones. For programming purposes, the zone numbers
are 1 through 6. See the Compliance Listing Guide (LT-2779) for a list of the compatible 2-wire smoke detectors. Do not
mix detectors from different manufacturers on the same zone.
Caution: Performing a Sensor Reset momentarily drops power to the devices on zones 1-6. The panel views these
zones as Open while power is absent.
When wiring powered zones for 2-wire smoke detectors, refer to the following specifications:
Maximum wire length—3000 feet (18 AWG) or 1000 feet (22 AWG)
Maximum voltage—28 VDC
Maximum normal standby current—7.5 mA DC
Maximum line impedance—100 Ohms
Maximum short circuit current—63 mA
The voltage sensing Terminal measures the voltage across a 3.3k Ohm EOL resistor to ground. Use Model 309 3.3k Ohm
resistors. Dry contact sensing devices can be used in series (normally-closed) or in parallel (normally-open).
Terminal
20
Operational Parameters
Each protection zone detects three conditions: Open, Normal, and Short.
Zone Response Time
A condition must be present on a zone for 500 milliseconds before it is detected by the panel. Ensure detection devices
used on the protec tion zones are rated for use with this delay. Zones 1-6 can also be programmed for a fast response
delay of 160 milliseconds.
Contact
Normally Closed
Common
Normally Open
Digital Monitoring Products
12
Function
17
Zone 1 positive
18
Zone 1 negative
19
Zone 2 positive
Zone 2 negative
21
Zone 3 positive
22
Zone 3 negative
Terminal 13‑24 Specifications
Condition
Resistance on zone
Open
Over 6600 ohms
Normal
1650 to 6600 ohms
Short
Under 1650 ohms
Protection Zone Parameters
Output 1
Color
Violet
Gray
Orange
Model 431 Output Wiring
Terminal
23
24
25
26
27
28
Voltage on positive terminal
Over 25.3 VDC
21.2 to 25.3 VDC
Under 21.2 VDC
Output 2
Contact
Normally Closed
Common
Normally Open
XF6 Series Installation and Programming Guide
Function
Zone 4 positive
Zone 4 negative
Zone 5 positive
Zone 5 negative
Zone 6 positive
Zone 6 negative
Color
Violet with white stripe
White with gray stripe
Orange with white stripe