SYSTEM COMPONENTS

Figure 1 shows some of the accessory modules you can connect for use in various applications. A brief description of
each module follows in the Accessory Devices section.
Form C Relays (OUT 1 and OUT 2)
Output Color Code–Model 431
Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Annunciator Outputs (OUTPUTS 3-6)
Output Color Code
Output 3
Red
Output 4
Yellow
Output 5
Green
Output 6
Black
AC Wiring must be in conduit and exit out
the left side of the enclosure.
Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.
AC
AC
+B
–B
BELL GND
RED YEL GRN BLK
SMK GND
Z1
1
2
3
4
5
6
7
8
9
10
11
12
13
1/4"
NFPA 72
This equipment should be
installed in accordance with
Chapter 11 of the National Fire
Alarm Code, ANSI/NFPA
72-2002, (National Fire
Protection Association,
Batterymarch Park, Quincy,
MA 02269). Printed
information describing proper
installation, operation, testing,
maintenance, evacuation
planning, and repair service is
to be provided with this
equipment.
All circuits are inherently
Power Limited except the red
battery wire and AC terminal.
DMP Transformer
16 VAC 56 VA
Class 2 Wire-in
Secondary Power
Supply
1.0 Amps Max. charging
current. Use only 12 VDC
rechargeable batteries.
DMP Models 364, 365,
366, 368, or 369. Replace
batteries every 3 to 5
years.
Bell
12 VDC nominal
Minimum cuto time is
5 minutes.
0.7 Amp Max
Keypads
Model 630F
60 mA at 8 to 14.5 VDC
CAUTION: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE RUN
TO PROVIDE SUPERVISION OF
CONNECTIONS.

Lightning Protection

Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on panel input and output
circuits. Additional surge protection is available with Model 370 or 370RJ Lightning Suppressors. For more information,
refer to the 370/370RJ Installation Sheet (LT‑0181).

Network Surge Protection

The Model 270 Network Transient Suppression Module protects the panel from surges on the Ethernet port. For more
information, refer to the Model 270 Installation Guide (LT‑1316).
XR150FC/XR550FC Series Installation Guide
Power
LED
PHONE LINE
OUTPUTS 3-6
Battery
Bell cuto
time
Start
range is 5 to 99
minutes marchtime
and non-coded.
AC
AC
+B
–B
BELL GND
RED YEL GRN BLK
1
2
3
4
5
6
7
8
9
s
s
s
s
s
s
s
Earth Ground
1.5k
Fire Command Center
POWER
TROUBLE
ALARM
SILENC E
ABC
DEF
GHI
JK L
RESET
1
2
3
4
ENABLE
MN O
P QR
STU
V WX
TES T
5
6
7
8
YX
DRIL L
COMMAND
9
0
Use UL Listed
Power Supervision
Relay rated at
12 VDC.
WARNING: Incorrect
connections may cause
damage to the unit.
Figure 1: XR150FC/XR550FC Series Wiring Diagram
XR550FC Series
Panel
TAMPER
PROG
SMK GND
Z1
GND
Z2
Z3
GND
Z4
Z5
GND
10
11
12
13
14
15
16
17
18
19
20
s
s
s
s
s
s
s
s
s
s
Listed Resistors
1.0k Ohm—DMP Model 311
3.3k Ohm—DMP Model 309
s
s
10K Ohm—DMP Model 308
s
s
Auxiliary Power
Total current combined from
Terminals 7, 11, 25, 27, and
LX500-LX900
0.5 Amp Max
RED
YELLOW
GREEN
BLACK
s
s
Zone Expander
Expander
Model 714
Model 711
7 mA @ 12 VDC
7 mA @
Models 714-8, 714-16
12 VDC
20 mA @ 12 VDC
s
s
s
s
s
s
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM
VERIFICATION FEATURE THAT RESULTS IN DELAY OF THE
SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS. THE
TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS)
SHALL NOT EXCEED 60 SECONDS. NO OTHER SMOKE
DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS
UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING
s
s
Activity
Link
LED
LED
(Yellow)
(Green)
ETHERNET
Heat detectors, pull
LOAD
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones 9
RESET
and 10.
Zones 9 and 10 and
Model 715 compatibility
CELL
identifier: A
MODULE
LX
Maximum operating
range: 9.8 VDC to
Class B (Style A).
Zones 9, 10, and all
expanded zones are
suitable for Class B (as
Z10+
Z6
Z7
GND
Z8
Z9+ Z9–
Z10–
applicable for the
initiating and signaling
line circuits per
21
22
23
24
25
26
27
28
ANSI/UL 864 Table
48.2 or 48.3).
Installation limits under
local Authority Having
s
s
s
s
s
s
Jurisdiction (AHJ).
Using verification
delays on zones 9 and
s
s
s
s
10 is optional. Use the
delays marked on the
smoke detectors or the
smoke detector
s
= Supervised Circuit
installation wiring
diagram.
Verification
Control Unit
Smoke
Zones
Delay
Model
______
13.6 sec
______
Zone Expander
RED
Model 715
7 mA @ 12 VDC
Models 715-8, 715-16
20 mA @ 12 VDC
Zone
Zone
Expander (up
to 8 zones)
s
s
s
s
Model 712-8
19 mA @
12 VDC
s
s
s
s
WARNING
JURISDICTION (AHJ).
Digital Monitoring Products
Front
Tamper
Rear
Tamper
14.0 VDC.
Detector
Delay
____sec
s
s
s
s
3