3. Notice each connector is labeled for your wire termination reference. Using a 3 mm flatblade
screwdriver, loosen the terminals and insert each of the data + and data - wire set into the
appropriate terminal for the circuit.
a. Terminate the violet (typical) control wire of the first pair into the + terminal associated to
the power circuit.
b. Terminate the gray (typical) control wire of the first pair into the - terminal associated to
the power circuit.
c. Tighten each screw terminal until the wire is secure.
4. Repeat steps 1–3 for the remaining outputs in the panel.
5. Noting the connector orientation, plug one end of the supplied wire harness into the five pin
connector on the upper right corner of the option card.
6. Noting the connector orientation, plug the other end of the wire harness into the "Option 1"
or "Option 2" connector labeled on the lower edge of the EchoDINcontroller.
Note:
enclosure. The graphic below shows the PCP-Mk2, option cards, and power supply in the
same DIN rail enclosure for clarity.
D
A PCP-Mk2
B 0–10 V option card
C DALI option card or Contact Input option card
See
Connect Control Wiring on page 4
PCP-Mk2.
Power Control Processor Mk2
It is not a requirement that system components be housed in a single DIN rail
A
E
B
C
D PCP-Mk2 option card connection
E Option card connection
for a detailed view of connections on the bottom of the
Page 11 of 15
ETC

Advertisement

loading
Need help?

Need help?

Do you have a question about the EchoDIN Power Control Processor Mk2 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

This manual is also suitable for:

Echodin-pcp-mk2