Field Settings for Indoor Unit
1.2
List of Field Settings for Indoor Unit
First
Mode
Code
Setting Contents
No.
No.
(Note 2)
Filter
cleaning
sign
interval
0
0
Filter sign setting
1
Filter type
10 (20)
1
Filter cleaning sign interval
2
Remote controller thermistor
3
Filter cleaning sign
Information for intelligent
5
Touch Manager / intelligent
Touch Controller
Remote controller thermistor
6
control during group control
Time for absence area
7
detection
Auxiliary electric heater ON
1
temperature: Ton
Auxiliary electric heater
1
ON/OFF temperature:
Ton/Toff
Auxiliary electric heater OFF
2
temperature: Toff
Setting of airflow rate when
3
heating
3
Electric heater setting
Electric heater capacity
5
setting
11 (21)
Detection rate setting
6
Automatic airflow adjustment
7
Compensating the
8
temperature around people
Compensating the floor
9
temperature
Dry mode set temperature
12
0
Optional output switching
1
External ON/OFF input
2
Thermostat switching
Airflow setting when heating
3
thermostat is OFF
12 (22)
Setting of operation mode to
4
AUTO
Auto restart after power
5
failure
Airflow setting when cooling
6
thermostat is OFF
155
01
Ultra long life
Approx.
filter
10,000
Long life filter
Approx.
Light
Standard filter
Approx.
Light
Long life filter
Short interval
Displayed
Not permitted
30 minutes
Standard
High sensitivity
OFF
Suction air
temperature only
–4°C (–7.2°F)
Room
temperature
1°C (1.8°F)
LL tap
OFF
LL tap
Second Code No.
02
Approx.
5,000
hrs.
hrs.
Approx.
2,500
Heavy
1,250
hrs.
hrs.
Approx.
200
100 hrs.
hrs.
Heavy
Ultra long life filter
Long interval
Refer to page on the right for details.
Not displayed
Refer to page on the right for details.
Permitted
60 minutes
Refer to page on the right for details.
Slightly increased
Refer to page on the right for details.
Refer to page on the right for details.
Low sensitivity
Completion of
airflow adjustment
Priorities given on
the suction air
temperature
–2°C (–3.6°F)
Same as cooling
mode set
temperature
Refer to page on the right for details.
Refer to page on the right for details.
0.5°C (0.9°F)
Set fan speed
Refer to page on the right for details.
ON
Set fan speed
: Factory setting
03
04
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Increased
—
Infrared
Standard
presence
sensitivity
sensor
disabled
Start of airflow
—
adjustment
Priorities given
Standard
on the floor
temperature
0°C (0°F)
+2°C (+3.6°F)
—
—
—
—
OFF
—
—
—
OFF
—
Part 5 Field Settings and Test Operation
SiUS342303E
Reference
Page
161
161
161
161
161
163
163
162
163
164
165
166
166
167
167
168
168
169
169
169
170
170
170
170
171