Field Setting from Outdoor Unit
[2-65]: Heat pump lockout temperature
Heat pump would be locked out when the outdoor air temperature is smaller than the Heat Pump
Lockout Temperature below – this setting is only affective when heat pump lockout mode has
been set. Unit will switch to heat pump lockout.
Heat pump lockout
209
Fahrenheit (°F)
temperature
0 (default)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Celsius (°C)
–15
–26.1
–10
–23.3
–5
–20.5
0
–17.7
5
–15
10
–12.2
15
–9.4
20
–6.6
25
–3.8
30
–1.1
35
1.6
40
4.4
45
7.2
50
10
Forced heat pump lockout
SiUS342303E
Part 5 Field Settings and Test Operation