Daikin VRV EMERION RXYQ-AATJA Service Manual page 176

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Field Settings for Indoor Unit
1.4.14 Dry Mode Set Temperature (for FXZQ-TB, FXUQ-PA, FXSQ-TB, and
FXMQ-TB models)
1.4.15 Optional Output Switching
Using this setting, "operation output signal" and "abnormal output signal" can be provided. Output
signal is output between terminals X1 and X2 of "adaptor for wiring", an optional accessory.
Mode
12 (22)
1.4.16 External ON/OFF Input
This input is used for "ON/OFF operation" and "Protection device input" from the outside. The input
is performed from the T1-T2 terminal of the operation terminal block in the electrical component
box.
Mode
12 (22)
169
Mode No.
First Code No.
11 (21)
12
First Code
Second Code
No.
No.
No.
01
02
03
04
0
05
06
07
First Code
Second
No.
No.
Code No.
01
02
03
1
04
05
06
07
Second Code No.
01
02
Same as cooling mode set temperature
Indoor unit thermostat ON/OFF signal is provided.
Output linked with "Start/Stop" of remote controller is provided.
In case of "Error Display" appears on the remote controller, output is
provided.
Only for FXSQ-TB, FXMQ-PB, FXMQ-TB
Economizer (field supply) ON/OFF signal is provided.
F2 T1 T2
Forced stop
Input A
ON: Forced stop (prohibition of using the remote controller)
OFF: Permission of using the remote controller
OFF  ON: Permission of operation
ON  OFF: Stop
ON: Operation
OFF: The system stops, then the applicable unit indicates A0. The other
indoor units indicate U9.
Only for FXMQ-PB
ON: Economizer (field supply) is connected.
OFF: Not connected
Only for FXSQ-TB, FXMQ-TB
ON: Economizer (field supply) is connected.
OFF: Not connected
SiUS342303E
: Factory setting
Contents
Room temperature
: Factory setting
Contents
: Factory setting
Contents
Part 5 Field Settings and Test Operation