Daikin VRV EMERION RXYQ-AATJA Service Manual page 40

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

Specifications
Model name (Combination unit)
Model name (Independent unit)
Power supply
1 Cooling
Nominal
capacity
Rated
2 Heating
Nominal
capacity
Rated
Casing color
Dimensions: (H × W × D)
Heat exchanger
Compressor Type
Volume
Number of
revolutions
Motor output ×
Number of units
Starting method
Fan
Type
Motor output ×
Number of units
Airflow rate
Drive
Connecting
Liquid pipe
pipes
Gas pipe
Weight
Sound pressure level
(Reference data)
Sound power level
(Reference data)
Safety devices
Defrost method
Capacity control
Refrigerant
Refrigerant name
Charge
Control
Standard accessories
Drawing No.
Notes:
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Rated capacity is certified under AHRI standard 1230.
1.
Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Rated capacity is certified under AHRI standard 1230.
2.
33
RXYQ312AAYDA
RXYQ144AAYDA
RXYQ168AAYDA
3 phase, 460 V, 60 Hz
312,000 (91.4)
Btu/h
(kW)
296,000 (86.7)
351,000 (103)
Btu/h
(kW)
320,000 (93.8)
Ivory white (5Y7.5/1)
65-3/8 × 48-13/16 × 30-1/8 + 65-3/8 × 48-13/16 × 30-1/8
in. (mm)
(1,660 × 1,240 × 765 + 1,660 × 1,240 × 765)
Cross fin coil
Hermetically sealed scroll type
m³/h
(11.6 + 17.6) + (13.8 + 21)
r/min
(5,496 + 5,196) + (6,504 + 6,204)
kW
(3.36 + 5.41) × 1 + (3.97 + 6.46) × 1
Propeller fan
kW
0.65 × 2 + 0.65 × 2
cfm
9,935 (281.3) + 9,935 (281.3)
(m³/min)
 3/4 (19.1) C1220T (brazing connection)
in. (mm)
 1-3/8 (34.9) C1220T (brazing connection)
in. (mm)
lbs (kg)
761 (345) + 761 (345)
dB(A)
dB
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
%
lbs (kg)
25.8 (11.7) + 25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
Soft start
Direct drive
69
89
Deicer
1-100
R-410A
4D144731
RXYQ336AAYDA
RXYQ168AAYDA
RXYQ168AAYDA
3 phase, 460 V, 60 Hz
336,000 (98.5)
320,000 (93.8)
378,000 (111)
338,000 (99.1)
Ivory white (5Y7.5/1)
65-3/8 × 48-13/16 × 30-1/8 + 65-3/8 × 48-13/16 × 30-1/8
(1,660 × 1,240 × 765 + 1,660 × 1,240 × 765)
Cross fin coil
Hermetically sealed scroll type
(13.8 + 21) + (13.8 + 21)
(6,504 + 6,204) + (6,504 + 6,204)
(3.97 + 6.46) × 1 + (3.97 + 6.46) × 1
Soft start
Propeller fan
0.65 × 2 + 0.65 × 2
9,935 (281.3) + 9,935 (281.3)
Direct drive
 3/4 (19.1) C1220T (brazing connection)
 1-3/8 (34.9) C1220T (brazing connection)
761 (345) + 761 (345)
69
89
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
Deicer
1-100
R-410A
25.8 (11.7) + 25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
4D144732
Part 1 General Information
SiUS342303E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vrv emerion rxyq-aayda