1. Turn OFF the power supply.
2. Measure the resistance between phases of U, V, W at the motor side connectors (3-core wire)
FXDQ07-12M
FXDQ18/24M
FXHQ12M
FXHQ24/36M
FXSQ54TB, FXMQ15-54PB, FXMQ30-54TB
Remove the X1A connector from the fan PCB (A2P) and measure the resistance between the U
and V, V and W, and W and U phases of the motor connector (with five conductors) and check that
each phase are balanced (within a permissible dispersion range of ±20%).
387
to check that the values are balanced and there is no short circuiting, while connector or relay
connector is disconnected.
Red
White
Black
Model
Black-Red
71.0  ± 10%
39.2  ± 10%
71.0  ± 10%
53.5  ± 10%
U
Measure the
resistance values
V
between phases
U, V, W.
W
Judgment
Black-White
73.5  ± 10%
41.3  ± 10%
73.5  ± 10%
31.6  ± 10%
Connector power wire use (X1A)
Red
(5)
U
(4)
White
(3)
V
(2)
W
Black
(1)
SiUS342303E