SiUS342303E
Model name
Power supply
1 Cooling
Nominal
capacity
Rated
2 Heating
Nominal
capacity
Rated
Casing color
Dimensions: (H × W × D)
Heat exchanger
Compressor Type
Volume
Number of
revolutions
Motor output ×
Number of units
Starting method
Fan
Type
Motor output ×
Number of units
Airflow rate
Drive
Connecting
Liquid pipe
pipes
Gas pipe
Weight
Sound pressure level
(Reference data)
Sound power level
(Reference data)
Safety devices
Defrost method
Capacity control
Refrigerant
Refrigerant name
Charge
Control
Standard accessories
Drawing No.
Notes:
Indoor temp.: 80°FDB (26.7°CDB), 67°FWB (19.4°CWB) / Outdoor temp.: 95°FDB (35.0°CDB) / Rated capacity is certified under AHRI standard 1230.
1.
Indoor temp.: 70°FDB (21.1°CDB) / Outdoor temp.: 47°FDB (8.3°CDB), 43°FWB (6.1°CWB) / Rated capacity is certified under AHRI standard 1230.
2.
Part 1 General Information
RXYQ216AATJA
3 phase, 208/230 V, 60 Hz
216,000 (63.3)
Btu/h
(kW)
206,000 (60.4)
243,000 (71.2)
Btu/h
(kW)
232,000 (68.0)
Ivory white (5Y7.5/1)
in. (mm)
65-3/8 × 68-7/8 × 30-1/8 (1,660 × 1,750 × 765)
Cross fin coil
Hermetically sealed scroll type
m³/h
r/min
6,396 + 6,702
kW
(6.66 + 6.98) × 1
Propeller fan
kW
cfm
14,510 (410.8)
(m³/min)
 5/8 (15.9) C1220T (brazing connection)
in. (mm)
 1-1/8 (28.6) C1220T (brazing connection)
in. (mm)
lbs (kg)
dB(A)
dB
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
%
lbs (kg)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
21.7 + 22.7
Soft start
0.95 × 2
Direct drive
904 (410)
68
90
Deicer
3-100
R-410A
25.8 (11.7)
4D144723
RXYQ240AATJA
3 phase, 208/230 V, 60 Hz
240,000 (70.3)
228,000 (66.8)
270,000 (79.1)
249,000 (73.0)
Ivory white (5Y7.5/1)
65-3/8 × 68-7/8 × 30-1/8 (1,660 × 1,750 × 765)
Cross fin coil
Hermetically sealed scroll type
23.6 + 24.7
6,966 + 7,272
(7.26 + 7.58) × 1
Soft start
Propeller fan
0.95 × 2
14,510 (410.8)
Direct drive
 5/8 (15.9) C1220T (brazing connection)
 1-3/8 (34.9) C1220T (brazing connection)
904 (410)
69
90
High pressure switch, Fan driver overload protector,
Overcurrent fuse, Inverter overload protector,
Leak detecting device
Deicer
3-100
R-410A
25.8 (11.7)
Electronic expansion valve
Installation manual, Operation manual,
Connection pipes, Clamps
4D144723
Specifications