Daikin VRV EMERION RXYQ-AATJA Service Manual page 135

Hide thumbs Also See for VRV EMERION RXYQ-AATJA:
Table of Contents

Advertisement

SiUS342303E
 Assuming suction temperature has changed from 30°C (86°F) to 18°C (64°F) (F A):
Suction air thermistor is used for temperatures from 30C (86F) to 25C (77F) (F  D).
Remote controller thermistor is used for temperatures from 25C (77F) to 21C (70F) (D B).
Suction air thermistor is used for temperatures from 21C (70F) to 18C (64F) (B A).
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower near
the floor where the occupants are. When controlling by suction air thermistor only, the indoor unit
may therefore be turned off by the thermostat before the lower part of the room reaches the set
temperature. The temperature can be controlled so the lower part of the room where the occupants
are does not become cold by widening the range in which remote controller thermistor can be used
so that suction temperature is higher than the set temperature.
°F
°C
89.6
32
86.0
30
82.4
28
78.8
26
75.2
24
71.6
22
68.0
20
64.4
18
60.8
16
12
14
53.6
57.2
Range in which remote controller
thermistor can be used
 Assuming the set temperature in the figure above is 24°C (75°F), and the suction
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat sensor is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 25°C (77°F) (A  C).
Remote controller thermistor is used for temperatures from 25°C (77°F) to 28°C (82°F) (C D).
 Assuming suction temperature has changed from 28°C (82°F) to 18°C (64°F) (D  A):
Remote controller thermistor is used for temperatures from 28°C (82°F) to 23°C (73°F) (D B).
Suction air thermistor is used for temperatures from 23°C (73°F) to 18°C (64°F) (B  A).
Part 4 Functions and Control
TH1 = Ts + 1 ≤ 31°C
TH1 = Ts + 1.8 ≤ 87.8°F
16
18
20
60.8
64.4
68.0
temperature has changed from 18°C (64°F) to 28°C (82°F) (A D):
TH1 = Ts – 1°C
TH1 = Ts – 1.8°F
22
24
26
71.6
75.2
78.8
Range in which
suction air thermistor
can be used
Outline of Control (Indoor Unit)
TH1 = Ts + 12 ≤ 33°C
TH1 = Ts + 21.6 ≤ 91.4°F
TH1 = Ts + 10 ≤ 31°C
TH1 = Ts + 18 ≤ 87.8°F
28
30
32
34
82.4
86.0
89.6
93.2
Suction air temperature (TH1)
Differential
°C
°F
128