Field settings table
Breadcrumb
Field code
Setting name
Room
└─ Antifrost
1.4.1
[2-06]
Activation
1.4.2
[2-05]
Room setpoint
└─ Setpoint range
1.5.1
[3-07]
Heating minimum
1.5.2
[3-06]
Heating maximum
1.5.3
[3-09]
Cooling minimum
1.5.4
[3-08]
Cooling maximum
Room
1.6
[2-09]
Room sensor offset
1.7
[2-0A]
Room sensor offset
└─ Room comfort setpoint
1.9.1
[9-0A]
Heating comfort setpoint
1.9.2
[9-0B]
Cooling comfort setpoint
Main zone
2.4
Setpoint mode
└─ Heating WD curve
2.5
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
2.5
[1-01]
High ambient temp. for LWT main zone heating WD curve.
2.5
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
2.5
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
└─ Cooling WD curve
2.6
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
2.6
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
2.6
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
2.6
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
Main zone
2.7
[2-0C]
Emitter type
└─ Setpoint range
2.8.1
[9-01]
Heating minimum
2.8.2
[9-00]
Heating maximum
2.8.3
[9-03]
Cooling minimum
2.8.4
[9-02]
Cooling maximum
Main zone
2.9
[C-07]
Control
2.A
[C-05]
Thermostat type
└─ Delta T
2.B.1
[1-0B]
Delta T heating
2.B.2
[1-0D]
Delta T cooling
4P670988-1B - 2023.03
Range, step
Default value
R/W
0: Disabled
1: Enabled
R/W
4~16°C, step: 1°C
8°C
R/W
12~18°C, step: 1°C
12°C
R/W
18~30°C, step: 1°C
30°C
R/W
15~25°C, step: 1°C
15°C
R/W
25~35°C, step: 1°C
35°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
-5~5°C, step: 0,5°C
0°C
R/W
[3-07]~[3-06]°C, step: 0,5°C
23°C
R/W
[3-09]~[3-08]°C, step: 0,5°C
23°C
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0:
40°C
[2-0C]=1:
45°C
[2-0C]=2:
55°C
R/W
[9-01]~min(45, [9-00])°C, step: 1°C
[2-0C]=0:
25°C
[2-0C]=1:
25°C
[2-0C]=2:
25°C
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
[2-0C]=0:
18°C
[2-0C]=1:
5°C
[2-0C]=2:
18°C
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
15~37°C, step: 1°C
25°C
[2-0C]≠2:
[2-0C]=2:
R/W
37~60, step: 1°C
[2-0C]=2:
60°C
R/O
[2-0C]≠2:
37~55, step: 1°C
55°C
R/W
5~18°C, step: 1°C
7°C
R/W
18~22°C, step: 1°C
22°C
R/W
0: LWT control
1: Ext RT control
2: RT control
R/W
0: MMI requests (incl. quick logic)
1: 1 contact
2: 2 contacts
[2-0C]≠2:
3~10°C, step: 1°C
R/W
[2-0C]≠2 (Radiator):
[2-0C]=2:
5°C
R/O
[2-0C]=2 (Radiator):
10°C
R/W
3~10°C, step: 1°C
5°C
(*6) EKECBUA3V_(*7) EKECBUA6V_(*8) EKECBUA9W_(*9) BUH less_
Installer setting at variance with
default value
Date
Value
(*1) 300 Tank_(*2) 500 Tank_
(*3) *X*_(*4) *H*_(*5) *B*_
(*10) 11P_(*11) 16P