Daikin ERLA14D V3 Series Installer's Reference Manual page 243

Hide thumbs Also See for ERLA14D V3 Series:
Table of Contents

Advertisement

Bizone kit
ERLA11~16D + EBSH/X(B)11+16P30+50D
Daikin Altherma 3 R ECH₂O
4P663482-1C – 2023.05
Solar priority
#
Code
[9.O.8]
[C‑00]
Additionally to the settings listed below, make sure to also set [7‑02]=1 (i.e. [4.4]
Number of zones = Dual zone) when a bizone kit is installed.
See also
"6.2.3  Multiple rooms – Two LWT
4
zones" [
 200].
Bizone kit installed
#
Code
[9.P.1]
[E-0B]
Description
0 Yes: When solar energy is provided and
storage tank temperature is above limit
temperature, heat pump and boiler are
switched off.
1 No: Heat pump and boiler can operate also
while solar energy is provided.
zones"  [
Description
Bizone kit installed:
0 No : The system only has a main zone.
1 N/A
2 Yes: A bizone kit is installed in order to add
an additional temperature zone.
11
Configuration
|
4
  45] and
"Number of
Installer reference guide
243