Daikin ERLA14D V3 Series Installer's Reference Manual page 114

Hide thumbs Also See for ERLA14D V3 Series:
Table of Contents

Advertisement

8
|
Piping installation
Installer reference guide
114
2 Connect the shut-off valves using the flat gaskets (accessory bag) to the space
heating/cooling water pipes of the indoor unit.
3 Connect the space heating/cooling field piping to the shut-off valves using a
sealing.
Do NOT exceed the maximum tightening torque (Thread size 1", 25-30  N•m). To
avoid damage, apply the necessary countertorque with a suitable tool.
2
≤Ø7 mm
4 Connect the domestic hot water in and out pipes to the indoor unit.
Do NOT exceed the maximum tightening torque (Thread size 1", 25-30  N•m). To
avoid damage, apply the necessary countertorque with a suitable tool.
1
5 Cut open the top cover.
If the space heating/cooling or the domestic hot water pipes are directed upwards,
the top cover must be cut along the perforation with a suitable tool.
6 Support the water piping.
For rearward facing connections: Support hydraulic lines suitably according to the
spatial conditions. This is valid for all water pipes.
3
1
2
ERLA11~16D + EBSH/X(B)11+16P30+50D
Daikin Altherma 3 R ECH₂O
4P663482-1C – 2023.05

Advertisement

Table of Contents
loading

Table of Contents