9-2-2 M16YR Specifications
Appearance and Function
Technical Specification
M16YR Technical Specification Table
item
Model
Output Points
Output Points Type
Maximum output frequency
Working Voltage
Maximum
Resistive
Load
Inductive
Current
Maximum Voltage
Drop/conducing resistance
Minimum Load
Leakage Current
Maximum
ON > OFF
Output
Delay
OFF > ON
Time
Over Current Protection
Isolation Type
SINK /SOURCE Type
Chapter 9 Right Side Expansion Module Specifications
M M16R Appearance
Technical Specifications
M16YR
16
Single-End Relay Output
For ON/OFF,not for frequent exchange
<250VAC,30VDC
2A/single,8A/common
80VA(AC)/24VA(DC)
0.06V(Initial)
2mA/DC Power
-
10ms
N/A
Electromagnetic Isolation, 1500VAC,
1 minute
Bilateral device, can be arbitrarily set to SINK/SOURCE output
8