(Fixed by DIN RAIL)
Shockproof
Noise Suppression
Withstand Voltage
Status Indicator
M04TCR Status Indicator Table
Indicator
instruction
PWR Indicator
Power ON: Green Light
Power OFF: No Lights
RUN Indicator
Running: Green Light
ADC Indicator
ADC Converting: Yellow Light
ALM Indicator
On Alert: Red Light
ERR Indicator
In ERROR: Red Light
Wiring
Chapter 9 Right Side Expansion Module Specifications
8.4~150Hz Constant acceleration:19.6m/s^2(2G)
10G, 10 times each along the 3 axes (IEC61131-2 Standard)
10G, 3 times each along the 3 axes
1500Vp-p, Width: 1us
1500 VAC 1 minute (Between power terminals and input/output terminals, and between all
external terminals and the housing)
M04TCR Wiring
34