Conversion precision
AD Converter
Operating mode
Control cycle
Tuning
Insulation
Operating Ambient
Temperature
Relative Humidity
Altitude
Vibration Resistance
(Fixed by DIN RAIL)
Shockproof
Noise Suppression
Withstand Voltage
Status Indicator
M0202TH Status Indicator Table
Indicator
instruction
PWR Indicator
Power ON: Green Light
Power OFF: No Lights
RUN Indicator
Running: Green Light
ADC Indicator
ADC Converting: Yellow Light
ALM Indicator
On Alert: Red Light
ERR Indicator
In ERROR: Red Light
Chapter 9 Right Side Expansion Module Specifications
±0.5% (25°C±5℃)
±1% (0~55℃)
24-Bit
Common Specifications
PID Control
ON/OFF Control
1~100 Seconds
PID Auto Tuning
Between analog input and CPU:insulated(Digital isolators)
Between analog input channels:insulated(optocoupler isolator)
0~55℃
5 ~ 95% (non-condensing, RH-2)
≦2000m
5~8.4Hz Amplitude: 3.5
8.4~150Hz Constant acceleration:19.6m/s^2(2G)
10G, 10 times each along the 3 axes (IEC61131-2 Standard)
10G, 3 times each along the 3 axes
1500Vp-p, Width: 1us
1500 VAC 1 minute (Between power terminals and input/output terminals, and between all
external terminals and the housing)