14-3 Regular Maintenance

When the routine daily maintenance is required, the module should be serviced cyclically according to the
actual operating environment. The inspection should be executed according to daily maintenance items
after confirming that the ambient environment meets the environmental specifications that are specified
in Chapter 3. When discovering any abnormal signs, please make improvement immediately according to
the specified troubleshooting method.
14-3-1 Maintenance Tools
Screwdriver
Stain removing alcohol
Cleaning cotton rag
Swab
Multimeter
Temperature gauge
Hygrometer
14-3-2 Regular Maintenance Items
Regular maintenance items table.
No.
Inspection Item
Environmental
1
temperature and
humidity
2
Air
3
Power voltage
Dust/stain
4
attaching status
Module
5
installation status
Locking status of
6
connection area
between modules
Terminal
7
connection status
Appearance of
8
wiring cable
PLC System
9
diagnosis
Job Content
Measure with temperature
gauge and hygrometer.
Measure the corrosive gas
Measured the supplied AC
power.
Check the appearance
Check if the module is
securely installed.
If the locking of module
connection area is
detaching or loosening.
Check by plugging and
unplugging the connection
port.
If the wiring cable is
presenting any damage
signs.
Check the error record.
Chapter 14 Repairs and Maintenance
Judgment Standard
Must meet the environmental
specifications established for
the respective module.
Corrosive gas should not be
detected.
Must meet the power module
specifications.
Should be no dust and stains.
The module must be securely
installed.
The locking device of the
module connection area must
be located at the locking
position.
The terminal cannot present
any loosening signs.
The wiring cable should be
intact without any damage.
Caused by careless error.
4
M-Series PLC Expansion Module User Manual
Action
Confirm the reasons causing the
environmental change and then
remove the problem.
Confirm the power supply system.
Wipe off the dust and the stains.
For correct installation method,
please refer to "Installation and
Wiring" section.
Move the locking device of the
module connection area back to
the locking position.
Connect the terminal properly.
Replace the wiring cable.
For detailed troubleshooting,
please refer to "Expansion Module
Troubleshooting" section.