FATEK M Series User Manual page 70

Programmable controller expansion module
Hide thumbs Also See for M Series:
Table of Contents

Advertisement

Altitude
Vibration Resistance
(Fixed by DIN RAIL)
Shockproof
Noise Suppression
Withstand Voltage
Status Indicator
M16X Status Indicator Table
Indicator
instruction
PWR Indicator
Power ON: Green Light
Power OFF: No Light
1~16 Input Indicator
ON: Green Light
OFF: No Light
Wiring
Wiring of single-end common SINK input
Chapter 9 Right Side Expansion Module Specifications
≦2000m
5~8.4Hz Amplitude: 3.5
8.4~150Hz Constant acceleration:19.6m/s^2(2G)
10G, 10 times each along the 3 axes (IEC61131-2 Standard)
10G, 3 times each along the 3 axes
1500Vp-p, Width: 1us
1500 VAC 1 minute (Between power terminals and input/output terminals, and between all
external terminals and the housing)
Wiring of single-end common SINK input
3
M-Series PLC Expansion Module User Manual

Advertisement

Table of Contents
loading

Table of Contents