Preparation Of The Installation Site - Ferroli EGEA TECH 90 LT User, Installation, And Maintenance Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 112
6.3.2 Environmental conditions for operation
The device cannot operate in
rooms classified as environ-
ments with an explosive atmos-
PROHIBITION
phere or at risk of fire.
The general operation of the de-
vice is guaranteed by observing
the environmental conditions in-
ATTENTION
dicated.
The device was not designed to
be installed outdoors, but to be
used in a "closed" environment
ATTENTION
not exposed to bad weather with
an ambient temperature between
+4 °C / +43 °C.
For the correct operation of the device it is necessary that its
positioning meets the following requirements:
• away from heat sources,
• away from direct sunlight,
• away from air conditioning systems,
• in a dust-free environment.
The environmental conditions for operation are shown in the
table below.
Ambient external air temperature (min. / max.)
-5 °C / +43 °C
6.3.3 Physical characteristics of water
The Langelier index of the water, measured at the operating
temperature, must be between 0 and +0.4.
The device must not operate with water hardness of less than
12°F. Conversely, if the water hardness is very high (over
25°F), use a suitably calibrated and monitored water softener,
because the residual hardness must not drop below 15°F.
6.4

PREPARATION OF THE INSTALLATION SITE

Proper operation affects the life of the device and its compo-
nents, but above all it affects the efficiency of the system. We
recommend that you carefully follow the instructions below; our
Technical Assistance Office is available for any clarifications on
the matter.
EN
150
OBLIGATION
R290
The product must be installed in a suitable place, i.e. to allow
normal use and adjustment operations as well as routine and
extraordinary maintenance.
The place where it will be operated must, therefore, be pre-
pared according to the values shown in fig. 49.
The room must also be:
• Equipped with adequate water and electricity supply lines;
• Prearranged for the condensation water discharge connec-
tion;
• Prearranged with adequate water drains in case of boil-
er damage or safety valve intervention or the breakage of
pipes/connections;
• Equipped with possible containment systems in case of se-
cod. 3540000400 - Rev. 03 - 09/2023
EGEA TECH
During the design and construc-
tion phase of the systems, local
rules and regulations must be
complied with.
The equipment must be in-
stalled and operated by a qual-
ified
technician
ance
with
local
safety legislation and regulations.
Incorrect installation can cause
damage to property and injury to
people and animals; the manu-
facturer declines all responsibil-
ity for the consequences.
The air inlet and outlet of the ap-
pliance must be channelled to
the external environment as in-
dicated in paragraph 6.6 on page
151.
300 mm
300 mm
300 mm
fig. 49 - Minimum spaces
90 LT - 120 LT
in
accord-
health
and
300 mm

Advertisement

Table of Contents
loading

This manual is also suitable for:

Egea tech 120 lt

Table of Contents