Ferroli EGEA TECH 90 LT User, Installation, And Maintenance Manual page 155

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 112
EGEA TECH
6.8.1 Remote connections
Photovoltaic enabling
Verify that the following values are set:
P03=1 (see "2.8.9 Phv menu - EVU functionality - Photovoltaic fun-
ctionality" on page 128)
P04=offset (to be set, see "2.8.9 Phv menu - EVU functionality - Pho-
tovoltaic functionality" on page 128)
G01=0 (vedi "2.8.10 SG Menu - Smart Grid functionality (see also "6.8.1
Remote connections")" on page 129)
DIG2
Open
Normal operation
Operation in BOOSTER mode with Setpoint
Closed
+ Offset
EVU block enable
Verify that the following values are set:
P01=1 (see "2.8.9 Phv menu - EVU functionality - Photovoltaic fun-
ctionality" on page 128)
P02=mode with DIG1 input open (see "2.8.9 Phv menu - EVU functio-
nality - Photovoltaic functionality" on page 128)
G01=0 (see "2.8.10 SG Menu - Smart Grid functionality (see also "6.8.1
Remote connections")" on page 129)
In this configuration the water heater is subjected to an EVU
block by your electricity supplier.
DIG1
Open
Normal operation
Unit in Off / Standby (depending on
Closed
parameter P02)
SMART GRID enabling
Verify that the following values are set:
G01=1 (see "2.8.10 SG Menu - Smart Grid functionality (see also "6.8.1
Remote connections")" on page 129
G02=operating state offset 3 (to be set, see "2.8.10 SG Menu - Smart
Grid functionality (see also "6.8.1 Remote connections")" on page 129)
When G01=1 is set, the water heater will work in SMART GRID
mode according to the 4 possible operating states:
DIG1
DIG2
Open
Closed
Open
Open
Closed
Open
Closed
Closed
NOTE The effect of the change of state of the di-
gital inputs DIG1 and DIG2 is applied after 10 min.
NOTA
90 LT - 120 LT
PV
EVU
Operational status
1
STANDBY unit
2
Operation in ECO mode
Operation in BOOSTER mode with
3
Setpoint + Offset
Operation in BOOSTER mode with
4
Setpoint max
cod. 3540000400 - Rev. 03 - 09/2023
Remote connection mode
For connection to the digital inputs, the equipment is equipped
with an additional 6-conductor cable (DIG1=EVU/SG0= white/
brown cable, DIG2=PV/SG1= green/yellow cable, DIG3= grey/
pink cable) already connected to the main -board (located in-
side the device).
Remote connections to possible energy systems are the re-
sponsibility of the qualified installer (connection boxes, termi-
nals and connection cables).
The figures below give an example of a remote connection (fig.
61 and fig. 62), which must not be longer than 3 m.
fig. 61 - Example of remote connection
fig. 62
EN
155