How to Program
Motor Set-up
The Quick Menu Motor Set-up guides through the needed motor parameters.
2
2
Parameter
0-03 Regional Settings
0-06 GridType
1-10 Motor Construction
1-20 Motor Power
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
1-26 Motor Cont. Rated Torque
1-30 Stator Resistance (Rs)
1-37 d-axis Inductance (Ld)
1-39 Motor Poles
1-40 Back EMF at 1000 RPM
1-73 Flying Start
3-41 Ramp 1 Ramp Up Time
3-42 Ramp 1 Ramp Down Time 0.05-3600.0 s
4-12 Motor Speed Low Limit
[Hz]
4-14 Motor Speed High Limit
[Hz]
4-19 Max Output Frequency
Table 2.6 Motor Parameters
18
TR150 Programming Guide
Range
[0] International
[1] US
[0] -[132] see start -up wizard for
open loop application
*[0] Motor construction
[1] PM, non salient SPM
0.12-110 kW/0.16-150 hp
50.0-1000.0 V
20.0-400.0 Hz
0.01-10000.00 A
100.0-9999.0 RPM
0.1-1000.0
0.000-99.990
0-1000
2-100
10-9000
[0] Disabled
[1] Enabled
0.05-3600.0 s
0.0-400 Hz
0.0-400 Hz
0-400
BAS-SVP16A-EN - Rev. 2013-09-05
Default
Function
0
Size selected
Select operating mode for restart
upon reconnection of the frequency
converter to mains voltage after
power down
[0] Asynchron
Size related
Enter motor power from nameplate
data
Size related
Enter motor voltage from nameplate
data
Size related
Enter motor frequency from
nameplate data
Size related
Enter motor current from nameplate
data
Size related
Enter motor nominal speed from
nameplate data
Size related
This parameter is available only when
1-10 Motor Construction Design is set
to [1] PM, non-salient SPM.
NOTICE
Changing this parameter affects
settings of other parameters
Size related
Set the stator resistance value
Size related
Enter the value of the d-axis
inductance.
Obtain the value from the permanent
magnet motor data sheet. The de-axis
inductance cannot be found by
performing an AMA.
4
Enter the number of motor poles
Size related
Line-Line RMS back EMF voltage at
1000 RPM
0
Select [1] Enable to enable the
frequency converter to catch a
spinning motor
Size related
Ramp up time from 0 to rated
1-23 Motor Frequency
Size related
Ramp down time from rated
1-23 Motor Frequency to 0
0.0 Hz
Enter the minimum limit for low
speed
65
Enter the maximum limit for high
speed
Size related
Enter the maximum output frequency
value