Parameters

3.7 Main Menu - Analog In/Out - Group 6

Parameter group for setting up the analog I/O configu-
ration and the digital output. The frequency converter is
equipped with 2 analog inputs: Terminal 53 and 54. The
analog inputs can freely be allocated to either voltage
(0-10 V) or current input (0/4-20 mA)
3.7.1 6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
Range:
Function:
10 s
[1 - 99 s]
Enter the time-out time.
*
6-01 Live Zero Timeout Function
Option:
Function:
Select the time-out function. The function
set in 6-01 Live Zero Timeout Function is
activated, if the input signal on terminal 53
or 54 is below 50% of the value in
6-10 Terminal 53 Low Voltage, 6-12 Terminal
53 Low Current, 6-20 Terminal 54 Low Voltage
or 6-22 Terminal 54 Low Current for a time
period defined in 6-00 Live Zero Timeout
Time.
[0]
Off
*
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
Illustration 3.10 Live Zero Timeout Function
TR150 Programming Guide
3.7.2 6-1* Analog Input 53
Parameters for configuring the scaling and limits for
analog input 53 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
0.07 V
*
6-11 Terminal 53 High Voltage
Range:
10 V
*
6-12 Terminal 53 Low Current
Range:
4 mA
*
6-13 Terminal 53 High Current
Range:
20 mA
*
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
0
[-4999 -
*
4999 ]
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Size related
6-16 Terminal 53 Filter Time Constant
Range:
0.01 s
*
BAS-SVP16A-EN - Rev. 2013-09-05
Function:
[0 - 10
Enter the voltage (V) that corresponds to
V]
6-14 Terminal 53 Low Ref./Feedb. Value. The
value must be set at >1 V to activate 6-01 Live
Zero Timeout Function.
Function:
[0 - 10 V] Enter the voltage (V) that corresponds to the
high reference value (set in 6-15 Terminal 53
High Ref./Feedb. Value).
Function:
[0 -
Enter the low current value. This reference
20 mA]
signal should correspond to the low reference/
feedback value, set in 6-14 Terminal 53 Low Ref./
Feedb. Value. The value must be set at >2 mA to
activate the Live Zero Time-out Function in
6-01 Live Zero Timeout Function.
Function:
[0 - 20
Enter the high current value corresponding
mA]
to the high reference/feedback set in
6-15 Terminal 53 High Ref./Feedb. Value.
Function:
Enter the reference or feedback value that
corresponds to the voltage or current set in
6-10 Terminal 53 Low Voltage to 6-12 Terminal 53
Low Current.
Function:
[-4999 -
Enter the reference or feedback value
*
4999 ]
that corresponds to the voltage or
current set in 6-11 Terminal 53 High
Voltage to 6-13 Terminal 53 High
Current.
Function:
[0.01 -
Enter the time constant. This is a first-order
10 s]
digital low pass filter time constant for
suppressing electrical noise in terminal 53. A
high time constant value improves dampening