4-51 Warning Current High
Range:
Function:
Size
[ 0.0 -
Enter the I
related
194.0 A]
current exceeds this limit, a bit in the
*
statusword is set. This value can also be
programmed to produce a signal on the
digital output or the relay output.
4-54 Warning Reference Low
Range:
Function:
-4999
[ -4999 -
Enter the lower reference limit. When the
*
4999 ]
actual reference falls below this limit, the
display indicates Ref
can be programmed to produce a status
signal on terminal 27 or 29 and on relay
output 01 or 02.
4-55 Warning Reference High
Range:
Function:
4999.000
[Depend on
Use this parameter to set a higher
*
the value of
limit for the reference range.
4-54 Warning
When the actual reference exceeds
Reference Low-
this limit, the display reads Reference
4999.000]
High. Warning bit 19 is set in 16-94
Ext. Status Word. Output Relay can be
configured to indicate this warning.
LCP warning light does not light
when this parameter set limit is
reached.
4-56 Warning Feedback Low
Range:
Function:
-4999.000
[-4999.000-
Use this parameter to set a lower
*
Depend on the
limit for the feedback range.
value of 4-57
When the feedback falls below this
Warning
limit, the display reads Feedback
Feedback High]
Low. Warning bit 6 is set in 16-94
Ext. Status Word. Output Relay can
be configured to indicate this
warning. LCP warning light does
not light when this parameter set
limit is reached.
4-57 Warning Feedback High
Range:
Function:
4999.000
[Depend on
Use this parameter to set a higher
*
the value of
limit for the feedback range.
4-56 Warning
When the feedback exceeds this
Feedback Low
limit, the display reads Feedback
-4999.000]
High. Warning bit 5 is set in 16-94
Ext. Status Word. Output Relay can be
configured to indicate this warning.
LCP warning light does not light
when this parameter set limit is
reached.
TR150 Programming Guide
value. When the motor
HIGH
. The signal outputs
Low
BAS-SVP16A-EN - Rev. 2013-09-05
4-58 Missing Motor Phase Function
Option: Function:
NOTICE
This parameter cannot be adjusted while the
motor is running. Missing Motor Phase
Function is always disabled with PM.
Select On, to display an alarm in the event of a
missing motor phase. Select Off, for no missing motor
phase alarm. However the On setting is strongly
recommended to avoid motor damage.
[0]
Off No alarm is displayed if a missing motor phase occurs.
[1]
On
An alarm is displayed if a missing motor phase occurs.
*
3.5.4 4-6* Speed Bypass
Define the Speed Bypass areas for the ramps. Some
systems call for avoiding certain output frequencies or
speeds, due to resonance problems in the system. 3
frequency ranges can be avoided.
4-61 Bypass Speed From [Hz]
Array [3]
Range:
Function:
0 Hz
[0 - 400
Some systems call for avoiding certain output
*
Hz]
speeds due to resonance problems in the
system. Enter the lower limits of the speeds to
be avoided.
4-63 Bypass Speed To [Hz]
Array [3]
Range:
Function:
0 Hz
[0 - 400
Some systems call for avoiding certain output
*
Hz]
speeds due to resonance problems in the
system. Enter the upper limits of the speeds
to be avoided.
3.5.5 Semi-Automatic Bypass Speed Set-up
The Semi-Automatic Bypass Speed Set-up can be used to
facilitate the programming of the frequencies to be
skipped due to resonances in the system.
The following process is to be carried out:
1.
Stop the motor.