Parameters

3 Parameters
3.1 Main Menu - Operation and Display -
Group 0
Parameters related to the fundamental functions of the
frequency converter, function of the keypad keys and
configuration of the keypad display.
3.1.1 0-0* Basic Settings
0-01 Language
Option:
Function:
Defines the language to be used in the display.
[0]
English
*
[1]
Deutsch
[2]
Francais
[3]
Dansk
[4]
Spanish
[5]
Italiano
[28]
Bras.port
[255] No Text
0-03 Regional Settings
Option:
Function:
NOTICE
This parameter cannot be adjusted
while the motor is running.
To meet the needs for different default settings
in different parts of the world, 0-03 Regional
Settings is implemented in the frequency
converter. The selected setting influences the
default setting of the motor nominal frequency.
[0] Interna-
Sets default value of 1-23 Motor Frequency [50
tional
Hz].
[1] North
Sets the default value of 1-23 Motor Frequency to
America
60 Hz.
0-04 Operating State at Power-up
Option:
Function:
Select the operating mode upon reconnection of
the frequency converter to mains voltage after
power down when operating in Hand (local)
mode.
[0]
Resume
Resumes operation of the frequency converter
*
maintaining the same local reference and the
same start/stop condition (applied by [Hand On]/
[Off] on the keypad or Hand Start via a digital
TR150 Programming Guide
0-04 Operating State at Power-up
Option:
[1]
Forced
stop,
ref=old
0-06 GridType
Option:
[0]
200-240V/50Hz/IT-grid
[1]
200-240V/50Hz/Delta
[2]
200-240V/50Hz
[10]
380-440V/50Hz/IT-grid
[11]
380-440V/50Hz/Delta
[12]
380-440V/50Hz
[20]
440-480V/50Hz/IT-grid
[21]
440-480V/50Hz/Delta
[22]
440-480V/50Hz
[30]
525-600V/50Hz/IT-grid
[31]
525-600V/50Hz/Delta
[32]
525-600V/50Hz
[100] 200-240V/60Hz/IT-grid
[101] 200-240V/60Hz/Delta
[102] 200-240V/60Hz
[110] 380-440V/60Hz/IT-grid
[111] 380-440V/60Hz/Delta
[112] 380-440V/60Hz
[120] 440-480V/60Hz/IT-grid
[121] 440-480V/60Hz/Delta
[122] 440-480V/60Hz
[130] 525-600V/60Hz/IT-grid
BAS-SVP16A-EN - Rev. 2013-09-05
Function:
input as before the frequency converter was
powered down.
Uses saved reference [1] to stop the frequency
converter but at the same time retain the local
speed reference in memory before powering
down. After mains voltage is reconnected and
after receiving a start command (pressing [Hand
On] key or using her Hand Start command via a
digital input) the frequency converter restarts
and operates at the retained speed reference.
Function:
Select the grid type of the supply
voltage/frequency.
NOTICE
Not all choices are supported
in all power sizes.
IT grid is a supply mains, where
there are no connections to
ground.
Delta is a supply mains where the
secondary part of the transformer
is delta connected and one phase
is connected to ground.