Connection Of Accessories; External Co; Rh Sensors - Salda SMARTY RV Mounting And Installation Instruction

Table of Contents

Advertisement

Silencers
Filter sets
8.1.

CONNECTION OF ACCESSORIES

8.1.1.
FIRE PROTECTION SIGNAL INPUT (FIRE PROTECTION INPUT (NC))
Fire protection signal:
MCB:
X4: 1, 2
8.1.2.

EXTERNAL CO

Settings:
CO
converter (S-KCO2 or S-RCO2-F2)
2
converter is connected as 0-10 V input "SERVICE › SENSORS › 0-10 VDC SENSORS › AIR QUALITY SENSOR 1" (choose "Extract CO
1. Set the extract air CO
2
2. Set:
• "Air quality sensor MIN": 0
• "Air quality sensor MAX": 2000
reduction function is activated "SERVICE › MAIN › CO
3. CO
2
level: "ADJUSTER › MONITORING › EXTRACT AIR CO
4. To see the CO
2
Humidity RH converter (S-KFF-U) or room RH converter (S-RFF-U-D-F2)
1. Set that extract air RH converter is connected as 0-10 V input "SERVICE › SENSORS › 0-10 VDC SENSORS › AIR QUALITY SENSOR 1" (choose "Extract RH")
2. Set:
3. You can see the level of extract air RH in the tab "ADJUSTER › MONITORING › EXTRACT AIR RH"
20
| EN
MUTE 125X600
MUTE 125X900
Filter set Smarty 2R V (ePM10-50+ePM10-50-
2pcs.)
Filter set Smarty 2R V plus (ePM10-50+ePM10-
50-2pcs.)

/RH SENSORS

2
REDUCTION FUNCTION" (it controls recirculation damper and fans)
2
"
2
FIT000287
FIT000287
FIT000288
FIT000288
ACC005247
-
-
ACC005248
SMARTY RV v2021.1
")
2