CONTENT 2. SYMBOLS AND MARKING 3. SAFETY INSTRUCTIONS AND PRECAUTIONS 4. DIMENSIONS AND WEIGHT 5. ELECTRICAL DATA 6. CONSTRUCTION 7. OPERATING CONDITIONS PACKAGE 9. TRANSPORTATION 10. UNPACKING 11. STANDART PACKAGE OF COMPONENTS 12. PLACE REQUIREMENTS 13. MOUNTING 14. CONNECTION OF THE AIR DUCT 15.
In exceptional cases harmful gases could be drawn out of the chimney or extraction ducting back into the room. In this case we strictly recommend to turn off Salda Antifrost and use an external preheater for heat exchanger anti-frost protection (see Salda Antifrost function on the Remote controller manual).
QUANTITY ON THE PALLET RIRS V EKO 3.0 [mm] [mm] [mm] [units] 1200 1405 1620 1900 1405 1620 2200 1705 1020 1770 3500 1820 1130 2090 5500 1900 1440 2230 9. TRANSPORTATION Figure. 9.1. Lifting with forklift. Only a product placed on a pallet may be lifted in order to prevent damage to the casing. 10.
1900 VEL 1900 VWR 1900 VWL 2200 VE 2200 VW 3500 VE 3500 VW 5500 VE 5500 VW 12. PLACE REQUIREMENTS 1,5xL 1,5xL Min. distance to open the door - 1,5xL; Min. distance to open control box door - H > 400 mm. 13.
14. CONNECTION OF THE AIR DUCT Figure. 14.1. Circular air duct conection Figure. 14.2. Rectangular air duct conection D2 dimensions depend on unit. 15. CONNECTION DIAGRAM Figure. 15.1. RIRS 1200-1900 VE EKO 3.0 (* Placement of the component depends on model) Figure.
Figure. 15.4. RIRS 2500-5500 VW EKO 3.0 Figure. 15.5. Indication for duct connection. Figure. 15.6. Ventilated premises ODA - outdoor air; SUP - supply air; ETA - extract air; EHA - exhaust air. LIST OF COMPONENTS Plate heat exchanger Fire alarm damper actuator I Supply air fan Fire alarm damper actuator II Extract air filter...
The manufacturer does not assume any liability for personal injuries and property damage due to nonconformance with the provided instructions. 17. START-UP RECOMMENDATIONS 17.1. RECOMMENDATIONS BEFORE THE START OF THE UNIT (BEFORE THE FINAL USER) Prior to start-up the system must be thoroughly cleaned. Check whether: •...
Figure 18.2.1. RIRS 1200-1900 V EKO 3.0 Figure 18.2.2. RIRS 2500-5500 V EKO 3.0 18.3. HEAT EXCHANGER Be sure the unit is disconnected from power source before performing any maintenance or repair. Proceed to maintenance and repair after any rotation in the fan stopped. Clean it once a year.
Figure 18.4.1. RIRS 1200-1900 V EKO 3.0 Figure 18.4.2. RIRS 2500-5500 V EKO 3.0 19. AUTOMATIC CONTROL Supply air temperature can be adjusted according to the temperature measured by the supply or extracted air temperature sensor and the tem- perature which is set by the user on the remote control panel. User selected supply air temperature is maintained by the plate (or rotor) heat exchanger and additional electric and/or water heater (optional).
19.1. SYSTEM PROTECTION a) Several steps of protection are provided for protection of the water heater. First: if during cold periods the temperature of the outward water flow drops below +10 °C (as measured by the TV sensor), then the water heater valve actuator M6 is forced to open regardless the need for heat.
Figure 19.2.2. Microswitches 1 and 2 19.3. MODBUS ADRESSES Data Quan- Name ModBus func. tity of Description Values dress data 1 - a c t i v e , Antifrost 01h_Read_Coils Plate heat exchanger frost protection function o-passive 1 - a c t i v e , Fire 01h_Read_Coils Fire alarm...
ToutDoor 04h_Read_Input Ouside air temperature sensor value Hex: FFEC Twater 04h_Read_Input Return water temperature sensor value Hex: FFEC 19.4. ELECTRICAL CONNECTION OF THE HVAC UNIT Electrical connection can only be implemented by the qualified electrician in accordance with the applicable international and national electrical safety requirements and requirements for installation of electrical devices.
20. CONTROL BOARD RG1 LED indications of the controller Pic. 3a LED2 Air damper close LED9 Medium fans speed LED2 + LED3 Air damper open LED10 Minimal fans speed LED4 Water valve open LED11 Supply air fan speed reducing LED5 Water valve close LED12 Preheater...
20.1. LABELING, CHARACTERISTICS OF THE CONTROLLER AND THE SYSTEM COMPONENTS Contact Labeling Description Max. load Min. load type [ A ] [ mA ] L(230V/50Hz power supply) N(230V/50Hz power supply) Electric heater Electric preheater/rotor ON/OFF 230V/50Hz Voltage of Normal speed for air fans Voltage of Min speed for air fans Extract room(s) air fan.
Supply air fan 0-10V pressure transmitter Fire guard Additional heate exchanger guard DI Filter guard Fans guard Extract air temperature sensor Temp. and humidity sensor for extract air. Extract air humidyti sensor Supply air temperature sensor Supply air temperature sen- sor.
Description of visual filter warning Casing sound power level (Lwa) [ dB(A) ] ErP Compliance 2018 2018 2018 2018 Internet address for disassembly instructions www.salda.lt 1900 VER 1900 VER 1900 VWR 1900 VWL RIRS EKO 3.0 Declared typology bidirectional bidirectional...
Page 68
Pressure Pressure Pressure Pressure control control control control control control Casing sound power level (Lwa) [ dB(A) ] ErP Compliance 2018 2018 2018 2018 2018 2018 Internet address for disassembly instructions www.salda.lt | EN RIRS 1200-5500 V EKO 3.0 v2019.06...
Should any alterations be made in the products, this declaration will no longer apply. Notified body: VšĮ Technikos priežiūros tarnyba, Naugarduko g. 41, LT – 03227 Vilnius, Lithuania, identification number 1399. Quality: Salda UAB activities are in line with the international quality management system standard ISO 9001:2015. Date...
3.4. when the unit was used not for its original purpose. 3.5. Company SALDA UAB is not responsible for potential loss of property or personal injury in cases where AHU is manufactured without a control system and the control system will be installed by the client or third parties. The manufacturer’s warranty does not cover devices that will be damaged by installing the control system.
Page 73
Heat exchanger cleaning Every 3-4 Filter replacement months** Look at the product label. ** - At least. NOTE. The purchaser is required to fill in the “Product maintenance table”. MAN000126 MAN000126 Ragainės g. 100 +370 41 540 415 Šiauliai LT-78109, LITHUANIA office@salda.lt...
Page 74