7. START-UP: SINGLE UPS

INSPECTION BEFORE START-UP
1- Make sure all wires are tightly connected to terminal block. Any loose connection will produce overheating, failures, and damage to UPS.
2- Make sure all instructions of installation sections (3 & 4) have been performed correctly. Check wiring and breakers are correct.
3- Put the terminal block cover back in its position to avoid access to wiring.
4- Check Emergency Power Off (EPO) port is correct:
• EPO Port closed (Wired): EPO function disabled
• EPO port connected to an emergency switch: EPO function available by activation of Emergency Switch, which must be "Normally
Closed" type to guarantee that UPS will shut down when circuit opens.
5- Check Maintenance Bypass Switch (MBS) located in UPS rear panel is in UPS position and its safety cover plate is duly installed.
6- Make sure all external protection devices in input and output lines are set to open (OFF) position.
START-UP PROCEDURE. SINGLE UPS
1- Make sure all equipment connected to UPS are off.
2- Set ALL Battery Bank breaker to ON (in case UPS has XBAT connected)
3- Power-On input line at electrical board by setting Circuit Breaker to ON
4- Set AC INPUT Breaker to ON in UPS rear panel. LCD of UPS must turn on. Fans should start operating, and UPS will start self-diagnosis.
5- Set UPS Bypass breaker to "ON". If BYPASS mode is allowed, A short time later, the screen indicates that the UPS enters BYPASS mode.
In models with an LED on the front panel, the BYPASS LED should light up. The outputs of the UPS are powered, although UPS is still off.
In BYPASS mode, the output voltage comes directly from Bypass input without the UPS intervening.
6- Follow the UPS power-on procedure:
Touch CONTROL icon / Touch UPS ON/OFF command / Confirmation Question "TURN ON UPS?", Touch "YES".
7- A few seconds after, UPS should pass from BYPASS Mode to NORMAL Mode or AC Mode.
8- Sequentially, power-on each protected equipment. Front panel LCD should show the load increase as each equipment start.
9- Once all equipment is on, the total power consumption (load) should not exceed UPS capacity.
10- At this moment UPS working under NORMAL AC-MODE and the system is supplied by.
IMPORTANT NOTES:
1. Should any warning or failure message appear on Screen, or UPS operation is not as expected, check TROUBLESHOOTING section
in this manual.
2. If the UPS triggers input circuit breaker when being powered, UPS might be configured to operate at a different frequency than the
system it has been connected to. In this case, you should follow this procedure:
Set the AC Input Breaker (on UPS Back Panel) to OFF.
Open AC Input Breaker on Power Panel.
Start UPS pushing
When turning on your screen in Battery Mode, check configuration in SETTING→ADVANCE→USER→Electronic, review following
parameters:
- CVCF MODE: If this function is not required, set it to "Disable". So, UPS Will synchronize with AC Line frequency.
- OUTPUT FRE: If CVCF MODE is required, set parameter OUTPUT FRE to the same value AC Line frequency.
Turn off the UPS and repeat the startup procedure.
3. The UPS batteries may not be fully charged at the time of UPS installation. For the first time, the UPS will require approximately 10
hours to fully recharge the batteries.