Fault
Fuel Sensor Fault
Gen Over Frequency
IEEE C37.2 – 81 Frequency Relay
Gen Over Frequency Overshoot
IEEE C37.2 – 81 Frequency Relay
Gen Over Voltage
IEEE C37.2 – 59 AC Overvoltage Relay
Gen Phase Seq Wrong
IEEE C37.2 – 47 Phase Sequence Relay
Gen Reverse Power
IEEE C37.2 – 32 Directional Power Relay
Gen Short Circuit
IEEE C37.2 – 51 IDMT Short Circuit Relay
Gen Under Frequency
IEEE C37.2 – 81 Frequency Relay
Gen Under Voltage
IEEE C37.2 – 27 AC Undervoltage Relay
Mag-PU Fault
Oil Press Sender Fault
Oil Pressure Low
IEEE C37.2 - 63 Pressure Switch
Oil Pressure Low Switch
IEEE C37.2 - 63 Pressure Switch
Temp. Sender Fault

Adding New Language Files

The DSE Configuration Suite PC Software and DSE Con-
trol modules are able to have their default languages
changed to suit the end user.
Deep Sea Electronics® G8601 Controller Owner's Manual
Description
The module detects a condition that indicates the generator is
running when the DSE module has instructed it to stop.
The module detected that circuit to the engine fuel level sensor
had become open circuit.
The module detected that the generator output frequency had
risen above the Over Frequency Alarm Trip level for the config-
ured delay timer.
The module detected that the generator output frequency had
risen above the Over Frequency Overshoot Trip during the con-
figured Overshoot Delay timer whilst starting.
The module detected that the generator output voltage had ris-
en above the Over Voltage Alarm Trip level for the configured
delay timer.
The module detected that the phase rotation of the generator
was different to the configured Generator Phase Rotation Alarm
setting.
The module detected that the generator output kW had fallen
below the Reverse Power Trip for the configured delay timer.
The module detected that the generator output current had ris-
en above the Short Circuit Trip for the duration of the IDMT
function.
The module detected that the generator output frequency had
fallen below the Under Frequency Alarm Trip level for the con-
figured delay timer after the Safety On Delay timer had expired.
The module detected that the generator output voltage had fall-
en below the Under Voltage Alarm Trip level for the configured
delay timer after the Safety On Delay timer had expired.
The module detected that circuit to the magnetic pick up sensor
had become open circuit.
The module detected that circuit to the engine oil pressure sen-
sor had become open circuit.
The module detected that the engine oil pressure had fallen be-
low the Low Oil Pressure Shutdown Trip level after the Safety
On Delay timer had expired.
The module detected that the low oil pressure switch had acti-
vated after the Safety On Delay timer had expired.
The module detected that circuit to the engine coolant tempera-
ture sensor had become open circuit.

Obtain Files

The files are either obtained from the Deep Sea Elec-
tronics Technical Support Department, contact your Au-
thorized Industrial Service Dealer (IASD).