Controller Operation
Fault
Charger ID 0 to 3 Common Electrical Trip
Combined Mains Decoupling
Coolant Temp High
IEEE C37.2 – 26 Apparatus Thermal Device
DEF Level Low
Digital Input A to L
DPTC Filter
ECU Amber
ECU Data Fail
ECU Malfunc.
ECU Protect
ECU Red
Engine Under Speed
IEEE C37.2 - 14 Underspeed Device
Exp. Unit Failure
Fail to Synchronise
Flexible Sensor A to D High
18
Description
NOTE: Due to module configuration the alarm message that ap-
pears on the display may be different. For further details of mod-
ule configuration, contact your Authorized Industrial Service
Dealer (IASD).
The module detected that a battery charger connected by DSE-
Net® had issued a Common Electrical Trip Alarm.
The module detected that the mains supply failed when the gen-
erator was in parallel with it.
The module detected that the engine coolant temperature had
risen above the High Coolant Temperature Electrical Trip level
after the Safety On Delay timer had expired.
The module received a fault condition from the engine ECU
alerting about the DEF level.
NOTE: Due to module configuration the alarm message that ap-
pears on the display may be different. For further details of mod-
ule configuration, contact your Authorized Industrial Service
Dealer (IASD).
The module detected that a digital input configured to create a
fault condition became active and the appropriate LCD mes-
sage is displayed.
The module received a fault condition from the engine ECU
alerting that the DPF/DPTC had activated.
The module received an amber fault condition from the engine
ECU.
The module is configured for CAN operation but has not de-
tected data being sent from the engine's ECU.
The module received a malfunction fault condition from the en-
gine ECU.
The module received a protect fault condition from the engine
ECU.
The module received a red fault condition from the engine ECU.
The module detected that the engine speed had fallen below
the Under Speed Alarm Trip level for the configured delay timer
after the Safety On Delay timer had expired.
The module detected that communications to one of the DSE-
Net® expansion modules had been lost.
The module failed to synchronise the generator before the Fail
to Sync Delay timer had expired.
NOTE: Due to module configuration the alarm message that ap-
pears on the display may be different. For further details of mod-
ule configuration, contact your Authorized Industrial Service
Dealer (IASD).
The module detected that an analog input value had risen
above the Flexible Sensor High Alarm Trip level.