PIT es Set10u-5ns
Supplementary data
Permitted operating height
The values stated in the technical details apply to the use of the device in operating heights
up to max. 2000 m above sea level. When used in greater heights, constraints have to be
taken into account:
}
Permitted maximum operating height 5000 m
}
From an operating height of 2000 m the max. permitted ambient temperature is reduced
by 0.5 °C/100 m
Operating height
3000 m
4000 m
5000 m
Operating Manual PIT es Set10u-5ns
1004426-EN-01
Permitted ambient temperature
50 °C
45 °C
40 °C
| 23