Pilz PIT es Set10u-5ns Operating Manual page 17

Control and signal devices
Hide thumbs Also See for PIT es Set10u-5ns:
Table of Contents

Advertisement

PIT es Set10u-5ns
Defined properties of evaluation devices:
}
Dual-channel with detection of partial operation (only one channel of the input circuit is
open)
}
Detection of shorts across contacts and earth fault detection: Detection of shorts across
contacts is possible also via a positive and negative input circuit
}
Digital inputs type 2 in accordance with IEC 61131-2
}
Offset test pulses (not overlapping) with a maximum duration of the on/off test pulse of
7.5 ms
Connect the evaluation device as described in the evaluation device's operating manual.
Please note:
}
Protective separation of the outputs to voltages over 60 V
}
The power supply that feeds the evaluation device must meet the regulations for PELV in
accordance with EN 60204-1.
}
The evaluation device must meet the requirements in the
specified values must not be exceeded.
}
The LED safety printed circuit board built into the unit contains two permanently installed
blow-out fuses. If the fuses are tripped by overcurrent or overvoltage, the LED safety prin-
ted circuit board must be exchanged (see
Ensure the wiring and EMC requirements of IEC 60204-1 are met.
To connect the evaluation device to the E-STOP device, use a 5-pin unshielded cable with
an A-coded M12 female connector (see
cable").
To connect a decentralised module (e.g. PDP67 F 8DI ION from Pilz), use a 5-pin unshiel-
ded cable with an A-coded M12 male connector (for connection to the decentralised mod-
ule) and an A-coded M12 female connector (for connection to the E-STOP device) (see
der reference [
Operating Manual PIT es Set10u-5ns
1004426-EN-01
Order reference [
24]
"Connection cable for connection to decentralised modules").
Technical details [
Order reference [
24]).
24]
"Open-ended connection
20]. The
Or-
| 17