Examples For Connection To Pilz Evaluation Devices - Pilz PIT es Set10u-5ns Operating Manual

Control and signal devices
Hide thumbs Also See for PIT es Set10u-5ns:
Table of Contents

Advertisement

PIT es Set10u-5ns

Examples for connection to Pilz evaluation devices

Evaluation device
PNOZ s5
PNOZ m B0
PDP67 F 8DI ION
Operating Manual PIT es Set10u-5ns
1004426-EN-01
Internal supply voltage
PNOZ s5
S11
S21
S12
S22
A2
PNOZ m B0
T0
M20
T1
M21
IM0
IM1
A2
PDP67 F 8DI ION
1
5
2
4
3
NOTICE
Check wiring
Particularly if you are using an open-ended cable, check the function of the
E-STOP pushbutton before commissioning the plant/machine by interrupt-
ing the GND connection of PIN 3. The evaluation device must then switch
off. When an evaluation device does not switch off, there is a wiring error.
External supply voltage (24 V)
PIT es Set10u-5ns
(400 461)
1
5
2
4
3
PIT es Set10u-5ns
(400 461)
PNOZ m B0
1
5
2
IM0
4
IM1
3
A2
PIT es Set10u-5ns
(400 461)
1
5
2
4
3
L+
PIT es Set10u-5ns
(400 461)
1
5
2
4
3