Grounding; Input Power Requirements; Table 2-6 Input Currents For 3-Phase Input Power - Elgar TrueWave TW 5550 Operation Manual

Table of Contents

Advertisement

TW 3700 • TW 5550
2 .7 .5
GR OU NDI NG
The three waveform outputs (TRIGGER OUT, CLOCK & LOCK,
SYNC OUT) share the same ground. This ground should not exceed
20V Peak from chassis ground. If possible, this ground should be
connected to the chassis.
DFI, IEEE 488.2 and RS-232 share the same signal ground.
2 .8
I NP U T P OWE R R E QU I R E ME NT S
Input power is connected to the TW via the rear panel connectors. See Table 2-6 and
Table 2-7 for input current values. If it is required to shut the unit power off using the
front panel power switch, please wait at least 30 seconds before re-applying power.
WARNING! An overcurrent protection device (i.e., circuit breaker)
is required in the building installation. The circuit breaker should be
rated for continuous current as required by the TW system (see Table
2-2). Installation should comply with local safety standards.
A device to disconnect the TW system from the energy supply source
is also required. This switch or circuit breaker must be close to the
TW system, within easy reach of the operator, and clearly labeled as
the disconnection device for the TW system.
MAXIMUM LINE
TW 5550
PFC
USA
PFC
INTL
RECT
USA
RECT
INTL
TW 3700
PFC
USA
PFC
INTL
RECT
USA
RECT
INTL

Table 2-6 Input Currents for 3-Phase Input Power

REQ'D INPUT
TERMINAL JUMPER
CONNECTIONS
Elgar TrueWave
MAXIMUM
NEUTRAL
CURRENT
CURRENT
27A RMS
Not Required
14A RMS
14A RMS
42A RMS
Not Required
42A RMS
68A RMS
27A RMS
Not Required
14A RMS
14A RMS
28A RMS
Not Required
28A RMS
48A RMS
CONNECT
1-PHASE INPUT
VOLTAGE
POWER TO
F1-F3 FUSE
RECOMMENDED CIRCUIT
RATING
BREAKER RATING (MAX.)
40A
40A RMS
20A
20A RMS
50A
50A RMS
50A
50A RMS
40A
40A RMS
20A
20A RMS
40A
40A RMS
40A
40A RMS
MAXIMUM
F1-F3
INPUT
FUSE
CURRENT
RATING
Installation
RECOMMENDED
CIRCUIT BREAKER
RATING (MAX.)
2-9