Agency Requirements; Physical Specifications; Environmental Data - Elgar TrueWave TW 5550 Operation Manual

Table of Contents

Advertisement

TW 3700 • TW 5550
1 .8
AGE NCY R E QU I R E ME NT S
The TrueWave conforms to the following agency requirements:
• European Community CE, including:
EN61010-1 1993, Installation Category III
EN55011 Group 1, Class A
EN50082-1 1992
• FCC Part 15, Class A
1 .9
P H Y S I CAL S P E CI F I CAT I ONS
Height: 8.75" (222 mm)
Width: 19" (483 mm)
Depth: 23.5" (597 mm)
Weight: TW 3700 89 lbs. (40 kg),
TW 5550 115 lbs. (52 kg)
Cooling: Air is drawn in from the front, top, and sides and exhausted through the rear
of the chassis.
1 .1 0 E NVI R ONME NT AL DAT A
Operating Temperature: 0°C to 45°C (32°F to 113°F).
Note temperature measured at air inlet of TW. If cabinet mounted, cabinet inlet air may
be rated at lower maximum temperature due to warming of inlet air.
Storage Temperature: -40°C to 70°C ( - 40°F to 158°F).
Humidity (Non-condensing): 0 to 85% at 31°C (88°F);
derate to 50% at 40°C (104°F).
Operating Shock: 10g for 11 ms.
Operating Vibration: 1g, 5 to 55 Hz dwell on resonances for 2 minutes maximum.
Altitude: Operating 6,560 ft., Non-operating 40,000 ft.