Factory setting varies according to inverter capacity (kVA).
Capacity
Voltage Class
(kW)
(V)
0.1
0.25
200
0.55
Single-phase
1.1
1.5
3-phase
2.2
4.0
0.37
0.55
1.1
400
1.5
3-phase
2.2
3.0
4.0
(1) Reduce continuous output current when changing carrier frequency to 4
NOTE
(10 kHz) for the 200V class (1.5kW or more) and 400V class
inverters. Refer to the table above for the reduced current.
[Operation Condition]
• Input power supply voltage : 3-phase 200 to 230V (200V class)
• Ambient temperature
(2) If the wiring distance is long, reduce the inverter carrier frequency as
described below.
Wiring Distance between
Inverter and Motor
Carrier frequency
(n46 setting)
(3) Carrier frequency is automatically reduced to 2.5kHz when Reducing
carrier frequency selection at low speed (n75) is set to 1 and the
following conditions are satisfied:
Factory setting : 0 (Disabled)
58
Initial Setting
Carrier
Setting
Frequency
4
10kHz
4
10kHz
4
10kHz
4
10kHz
3
7.5kHz
3
7.5kHz
3
7.5kHz
3
7.5kHz
3
7.5kHz
3
7.5kHz
3
7.5kHz
3
7.5kHz
3
7.5kHz
3
7.5kHz
Single-phase 200 to 240V (200V class)
3-phase 380 to 460V (400V class)
: -10 to +50°C (14 to 122°F)
(Protection structure: open chassis type
IP20)
Up to 50m
10kHz or less
(n46=1,2,3,4,
7,8,9)
Output frequency à 5Hz
Output current Ä 110%
Maximum Continuous
Reduced Current
Output Current
(A)
0.8
1.6
3.0
5.0
8.0
11.0
17.5
1.2
1.8
3.4
4.8
5.5
7.2
9.2
Up to 100m
More than 100m
5kHz or less
2.5kHz or less
(n46=1,2,
(n46=1,
7,8,9)
(A)
----
7.0
10.0
16.5
1.0
1.6
3.0
4.0
4.8
6.3
8.1
7,8,9,)